- ページ 5
セキュリティセンサー Autonics PSAN SeriesのPDF 製品マニュアルをオンラインで閲覧またはダウンロードできます。Autonics PSAN Series 6 ページ。 Display type pressure sensors
Autonics PSAN Series にも: マニュアル (2 ページ), マニュアル (13 ページ), 製品マニュアル (7 ページ)
Output Operation mode
Change the output operation mode to change pressure detection method.
ON:
OFF:
■ Hysteresis
• Set the hysteresis for pressure detection
directly.
• Setting: Pressure detection level (ST1,
ST2), Hysteresis (HYS1, HYS2)
Pressure
H
ST2 / HYS2
H
ST1 / HYS1
OUT1 N.O.
ST1 / HYS1
OUT1 N.C.
ST1 / HYS1
OUT2 N.O.
ST2 / HYS2
OUT2 N.C.
ST2 / HYS2
■ Hysteresis - Window
comparison output
• It is available both hysteresis mode
and window comparison output mode
operations.
• Setting: Pressure detection level (ST1),
Hysteresis (HYS1), High limit (HIGH), Low
limit (LOW)
Pressure
A
HIGH
A
LOW
ST1
HYS1
OUT1 N.O.
ST1 / HYS1
OUT1 N.C.
ST1 / HYS1
OUT2 N.O.
LOW / HIGH
OUT2 N.C.
LOW / HIGH
■ Forced output control
• It displays the present pressure with
forcibly holding comparing output OFF
regardless of setting value.
• Manual ON/OFF for OUT1/2 is possible
by [M], [▼] or [▲] key during forced
output control operation.
[M]
[M]
[▼]
[▼]
[▼]
OUT1
Time
[▲]
[▲] [▲]
OUT2
Time
H: Hysteresis A: Min display interval
■ Window comparison output
• It detects pressure at the desired range.
• Hysteresis is fixed as min. display interval.
• Setting: High limit (HI1, HI2), Low limit
(LO1, LO2)
Pressure
A
HI2
A
LO2
A
HI1
A
LO1
Time
OUT1 N.O.
LO1 / HYS1
OUT1 N.C.
LO1 / HYS1
OUT2 N.O.
LO2 / HYS2
OUT2 N.C.
LO2 / HYS2
■ Auto sensitivity setting
• This function is to set the proper position
(SET) automatically by applied pressure
from two positions (ST1, ST2).
(ST1+ST2)
SET=
2
• Hysteresis is fixed as min. display interval.
Pressure
A
ST2
A
SET
A
ST1
Time
OUT2 N.O.
SET
OUT2 N.C.
SET
OUT1 N.O.
ST1/ST2
OUT1 N.C.
ST1/ST2
Zero-point Adjustment
With the pressure port open, the current pressure value on display is set to zero forcibly
by removing deviations from opening the pressure port. Zero-point adjustment affects
analog output.
• For precise measurement, execute zero-point adjustment periodically.
Maximum / Minimum Value Monitoring
Time
In order to identify abnormal conditions of the system that are not easily identified or to
diagnose the max. / min. input that has occurred, save the value and notify it.
• When the memorized max. / min. pressure is higher / lower than the rated pressure, it
displays 'HHHH' / 'LLLL'.
Input
Max. memorized input
Display / Output Scale
Customizes the scale of display / output value from rated output range. If the measured
input is a, b, and the arbitrary values to be displayed are A, B, the display / output value
are outputted for input a and b linearly (a = A, b = B).
Display / Output
Time
B
A
A
B
Input
Response Time
Prevents chattering of the output by changing the response time of the control output
and pressure display value.
When the response time is longer, the number of digital filter increase, so stable
measurement is possible, but the measured value may differ from the actual input
value.
Analog Output Characteristic
■ Input - Output
Voltage/
Current output
Max. Output
Min. Output
Rated input
range
Display input range
Output
0%
Input
Input
Min. memorized input
Time
Display / Output
Display / Output
A
B
A
B
Input
A
B
A
■ Linearity
Voltage/
Current output
Input
Time
B
Input
Linearity
Input