3. Troubleshooting / 4. Technical specification
3. Troubleshooting
PROBLEM
The safety valve does not open
{even doing a blow through).
Safety valve leaks.
Water from the water heater is dirty.
Warning!
1. At least once every 18 months replace the magnesium anode (keep the receipt for the magnesium anode). Regular replacement of the magnesium
anode is a requirement for maintaining a warranty on the tank (for an enamelled tank).
2. It is not allowed to install the water heater without a properly functioning safety valve.
3. The safety valve must be installed directly in front of the cold water pipe leading to the water heater. Only valves approved by the Technical Supervision
Office, designed for capacitive water heaters, can be used – ones with a return valve. The safety valve allows water to flow out of the heater, if an
excessive increase in pressure in the heater occurs – opening pressure of 0,67 MPa.
4. No additional device can be installed between the safety valve and the water heater (e.g. shut off valve, water valve, etc.).
5. The repair method is specified by the manufacturer.
6. In the event of product defects importer. Free repairs of damage, for which the manufacturer is liable, will be remedied within 14 days from the date
of notification. THE WATER HEATER MUST NOT BE DISASSEMBLED. The receipt for the purchase of the water heater must be kept for after sales service
purposes. The number of repairs does not include gasket replacements, magnesium anode replacements etc.
7. A properly filled out, complete and in no way corrected warranty card is the basis for having repairs done under warranty (it must be kept throughout
the warranty period).
8. Cases not covered by the above conditions are subject to the provisions of the Polish Civil Code.
9. Connections with the heaters must not be made of plastic pipes not designed to work at a temperature of 95°C and at a pressure of 1,0 MPa.
10. Water heaters must be installed in such a way as to ensure easy access (e.g. for maintenance, repair or replacement).
11. The manufacturer is not liable for any inconvenience or expense caused by the dismantling of additional housing elements.
1. In case water becomes odorous or darkly coloured, this is caused by the formation of hydrogen sulfide by sulfate reducing bacteria that live in oxygen
poor water. If cleaning the water heater, replacing the magnesium anode and setting the temperature above 60°C do not improve the situation, we
recommend the use of a titanium anode connected separately to the power supply.
4. Technical specification
Specification
storage capacity
*
Tank's maximum working temperature
Tank's maximum working pressure
Magnesium anode - top cover 5/4" plug
Height
Internal diameter
External diameter
Net weight
According to the (EU) 812/2013, 814/2013.
*
6
Installation and Operating Manual - SG(S) Fusion
CAUSE
Safety valve seized.
Touching surfaces of safety valve dirty or
defective.
Excessive water pressure in the network.
A large amount of sediment in the tank.
Worn out magnesium anode
unit
l
°C
MPa
mm
mm
mm
mm
kg
METHOD OF ELIMINATION
Clean or replace the valve.
Clean or scrub the touching surfaces of the safety valve.
Instal a flow control device.
Clean the tank of sediment.
Replace the magnesium anode - not covered by the warranty.
SG(S) Fusion 100
104
95
1
25x390
900
500
600
54