Product Installation Guidelines
Optional modes:
- 'Urinal' mode:
When a user is first detected in front of the sensor, the cycle is triggered so that a timer starts when the
user leaves. At the end of this timed period, the solenoid valve is actuated to flush the urinal and the cycle
is then reset.
- 'Pan' mode:
When a user is first detected in front of the sensor, a timer starts. After a pre-set time, if the user is still
there, the sensor decides that a full flush will be required, otherwise, only a half flush will be triggered.
This flush happens a set time after the user leaves the immediate vicinity
TROUBLE SHOOTING
PROBLEM
Sensor Not
Responding
False
Activation
No water flow
Continuous
water flow
Note: Before attempting to replace any of these items check that you have access to re-run the
connection leads. If you do not have access or you have any doubts please contact Galvin Specialised for
advice before commencing replacement.
© Galvin Engineering Pty Ltd
CAUSE
Damaged or scratched lens
Sensor lead damaged
No Power
Waving Hand too fast past the sensor
Transformer faulty
Electrical interference
Reflection from a light source
Sensor not responding
No power
Power supply leads joined incorrectly
Faulty solenoid valve
Water or structural damage to
electrical components
Incorrect connections
Damage to sensor lead or power
supply lead
Pressure exceeding 500kPa
Water corroded electrical
connections
Solenoid valve jammed open
Solenoid installed incorrectly
Version 2, 8 September 2021, Page 9 of 10
RECTIFICATION
Replace Sensor Unit
Replace sensor lead
Check power is reaching transformer
Slow down the action in front of the sensor
Replace transformer
Ensure electrical suppressors are installed
correctly
Re-align sensor or shield light source
Check fault relating to sensor
Check power is reaching transformer
Replace electronic components
Check electrical connections, Replace solenoid
valve
Replace damaged electrical components
Check all connections
Check and replace lead & controllers
Reduce pressure to solenoid to 350 kPa
Replace electronic components
Remove obstruction from solenoid valve
Reinstall valve correctly
Version 1, 8 September 2021, Page 9 of 10