コントロールユニット aguilera AE/SA-SEのPDF マニュアルをオンラインで閲覧またはダウンロードできます。aguilera AE/SA-SE 2 ページ。 Operation confirmation module
MODULE CODING
All algorithmic equipment must be coded with a number as corresponds to its personalization. The recording of the module
numbering can be carried out from:
1.
AE/SA-PRG manual address programmer. See the programmer's manual for its coding.
2.
Algorithmic Panel. See operating manual of the algorithmic panel for its coding.
Program a number between 1 and 125 as corresponds for its personalization. For the Algorithmic System the module
occupies a single position inside the algorithmic loop.
The identification number of the unit, as well as the operation pilot, is stored in EEPROM memory.
Before connecting the module to the algorithmic loop, verify the coding is correct.
INHIBITION OF FLASHING OF THE OPERATION PILOT
The operation pilot mode can be modified when carrying out the module coding. By default, the operating mode is
activated.
TECHNICAL CHARACTERISTICS
Power supply voltage:
18 ~27 V (AE/SA-CTL Algorithmic loop card).
Consumption when idle:
1.8 mA
Consumption in alarm state:
1.9 mA
Algorithmic loop wiring
2-wire. Recommended cross-section 1.5 mm
Removable jacks for all connections
Output:
Voltage-free contacts. (NO, COMMON, NC)
Relay characteristics:
Maximum resistive load = 1 A / 30 Vdc - 0.5 A / 125 Vac
Maximum switching voltage = 125 Vdc - 125 Vac
Maximum switching power = 30 W - 125 VA
Temperature range:
0º - +50º C (ambient temperature)
Humidity range:
Relative humidity 10% - 90% without condensation.
Casing material:
ABS
Luminous indicator:
Operation pilot:
Activation:
Size:
105 x 82 x 25 mm
Fastening:
4 holes, diam. 3.5 mm
Weight:
100 g.
Ae-man-824-0.0 v1.0
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
2
red flash (can be inhibited).
red intermittent
TECHNICAL MANUAL
OPERATION CONFIRMATION MODULE
MOD.: AE/SA-SE
Microprocessor-based unit designed to be used with the algorithmic fire detection panels of AGUILERA
ELECTRONICA, to manage communications and monitor one digital input and output signal.
It allows an operation to be carried out and its performance confirmed. It is equipped with:
§
A relay output with voltage-free contacts that actuates an operation. The three contacts are provided,
normally open, normally closed and common.
§
A digital input, to receive the operation confirmation signal.
mode control is selected as normally open or normally closed.
Selector SW2 on: In idle mode the input is closed.
Selector SW2 off: In idle mode the input is open.
The operation should be performed and confirmed in an interval programmed on the Algorithmic Panel.
This module is conceived for carrying out operations with firebreak doors, air conditioning dampers and opening
valves.
It includes:
•
Operation pilot: It indicate it is operating correctly, giving red-colored flashes through the status LED. The
flashing frequency depends on whether the equipment in idle or has an input activated. If the flashing were
annoying in particular cases, it can be inhibited individually.
•
Removable jacks, to facilitate connection in the field.
•
The circuit's protective case leaves the status LED of the unit visible.
•
Individual identification: Each module is identified individually with a number inside the installation loop. This
number is stored in EEPROM memory whereby it is kept even though the detector is without power for a long
period.
Ae-man-824-0.0 v1.0
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
By means of a selector (SW2), idle
TECHNICAL MANUAL