Advanced Setup
The TTC International interface is shipped to the
customer so that no setup work is required for
basic operation. Set points in automatic and
manual may be entered and the zone will be
controlled by turning "On" the zone power. Many
customers require advanced features to satisfy
their operation. This page will describe the basics
of "Advanced Setup". Please note that security
levels are not standard. To place security on the
TTC International Interface you must activate
security by selecting your own personalized
security codes.
Advanced Setup Guide – Level 2 Security to Change
#
Limit (default)
(0)
0 -10 (0)
(1)
0 -10 (0)
(2)
+/ -100ºF / 55ºC (20ºF / 11ºC)
(3)
0- 300 seconds (60)
(4)
-31 to 27 (0)
(5)
0 -1000ºF / 537ºC (20ºF / 11ºC)
(6)
0-1000ºF/537ºC (220ºF/104ºC)
(7)
-31 to 27 (0)
(8)
0 to 54.0 minutes (5)
(9)
0-1000ºF/537ºC (999ºF/537ºC)
(10) 0-1000ºF/537ºC (999ºF/537ºC)
(11) 0-100% (100%)
(12) 0-1000ºF/537ºC (50ºF/28ºC)
(13) 0-1000ºF/537ºC (100ºF/56ºC)
(14) 0 or 1 (0)
(15) 0 to 1000 seconds (0)
(16) 0- 2 (0 = all zones)
(17) 0- 2 (0 = all zones)
(18) 0- 4 (0)
(19) 0 or 1 (0)
(20) 0 or 1 (0)
(21) 0 or 1 (0)
(22) 0 or 1 (0)
(23) - - -
(24) - - -
(25) 0- 999 (none)
(26) 0- 999 (none)
(27) 0- 999 (custom)
(28) 0 (0)
(29) - - -
(30) - - -
(31) - - -
(32) - - -
(33) - - -
(34) - - -
(35) - - -
(36) - - -
(37) 000-999 (level 2)
Explanation (*saved in menu)
Restore mold setup – access advanced setup. 0 – view area. Select menu 1-10. Enter to restore
Save mold setup – access advanced setup. 1 – view area. Select menu 1-10. Enter to save
*
Boost temperature set point. 2 – view area. Amount of temperature added to automatic set point during a boost
*
Boost time set point. 3 – view area. The amount of time boost is active
Algorithm set point (view only). View auto tuning selection or manual tuning value.
*
Temperature deviation alarm set point. Actual temperature activates individual zone alarm at this amount +/- set point
Standby set point (individual). When standby is activated, all automatic zones in the standby group will control to this set point
*
*
Control algorithm adjustment (individual). 0 = auto selection. To view actual tuning value select code 4
Manual Selections: 10 to 17 fast tuning with increasing lag. 20 to 27 slow tuning with increasing lag
-1 = very fast tuning; -17 to -10 fast manifold tuning with increasing lag. -27 to -20 very fast tuning with increasing lag
-30 and -31 ultra fast low mass tuning. P = auto selection tune performed (view area)
T/C pinched detection time (individual). 0 = normal (98+% output, 20ºF / 11ºC in 5 minutes). Change alarm timer amount
*
Critical over temperature alarm. If this temperature is exceeded for 8 seconds, all zones in automatic are turned "Off"
*
Automatic set point limit. The maximum set point an operator can enter in automatic
*
Manual set point limit. The maximum set point an operator can enter in manual
*
Boost limit. The maximum amount of degrees an operator can raise or lower the zone(s) during a boost
*
Trim limit. The maximum amount of degrees an operator can permanently change the zone(s) during a trim
*
Enable material protection input. Must see input repeat in time selected or will activate standby group. 0 = "Off"; 1 = "On"
*
Material protection time. Amount of time from 22-132 VAC/VDC input signal to activate standby group unless signal repeats
Set standby group. Select zone(s) to go into standby when activated by remote input. 0 = all; 1 = display; 2 = store
*
*
Set slaved power-up group. Select zone(s) to heat within 20ºF / 11ºC of one another until set point. 0 = all; 1 = display; 2 = store
*
Power Priority™. 0 = (off). 1-4 = increased smoothing of power output. A = Power Priority™ is active (view area)
Enabled slaved power-up. 0 = "Off"; 1 = "On"
*
Degree F or C selection. 0 = "degree F"; 1 = "degree C"
Type J or K thermocouple selection. 0 = "type J"; 1 = "type K"
Zone power status on power up. 0 = "all zones turned Off"; 1 = "zones On when shut down last, stay On"
*
Reserved for future use
Reserved for future use
Security code level 1. You must be in level 2 to change. Refresh procedure available, call Gammaflux
Security code level 2. You must be in level 2 to change. Refresh procedure available, call Gammaflux
Zone finder (locate zones). Finds new hardware, to activate enter 999. Displays number of zones available in the system
LED test. To activate, enter 0. Turns "On" all LEDs for troubleshooting
Output module software version number (display only), select zone, version displayed
Output module software revision number (display only), select zone, revision displayed
T/C input software version number (display only), select zone, version displayed (16 zones per module)
T/C input software revision number (display only), select zone, revision displayed (16 zones per module)
Data concentrator software version number (display only), select zone, version displayed
Data concentrator software revision number (display only), select zone, revision displayed
Operator panel software version number (display only), version displayed
Operator panel software revision number (display only), revision displayed
Security level indicated. 0 = lockout; 1 = operator; 2 = supervisor; 0 - enter, drops one level
Elevate one security level at a time with your customized code
Setup Number
Scroll Up
C
0
0
Current Value
Scroll Down
Access/Exit
Advanced Setup
Press both select
buttons at the same
time, hold and release.
Selection LED's go
dark in advanced
setup mode.
Set individually by zone