- ページ 9

産業機器 ADF Web HD67506のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。ADF Web HD67506 18 ページ。

ADF Web HD67506 ユーザーマニュアル
Industrial Electronic Devices

GENERAL PARAMETER:

This section define the fundamental communication parameter of two buses, Modbus and Ethernet.
By pressing the
"General
Parameter" button from the main window for SW67506 (Fig. 3) the window
"General Paramater" appears (Fig. 4).
The window is divided in two section: one for the Ethernet and the other for the Modbus (Serial).
The means of the fields for Ethernet are:
In the field
"IP
ADDRESS" insert the IP address;
In the field
"SUBNET
Mask" insert the Subnet Mask;
In field "Gateway" insert the Defualt Gateway IP address for use the gateway in WAN or Internet. For
enable this feature is necessary to check the Gateway option;
In the field "Port" insert the number of port;
If the field "TCP" is checked the Ethernet protocol used is the TCP, otherwise if the field "UDP" is
checked the Ethernet protocol used is the UDP.
The means of the fields for Serial are:
In the field
"Baud
rate" the baudrate for the Serial is defined;
In the field "Parity" the parity for the Serial is defined;
In the field
"Timeout
(ms)" there is the maximum time that the device attends for the answer from
the Slave interrogated.
If the field "RS232" is checked, the serial line in use is the RS232; otherwise if field "RS485" is
checked, the serial line in use is the RS485;
In the subsection "Protocol" it is possible to select the protocol to use in Modbus line from the
following:
Modbus
RTU;
Modbus
ASCII;
JBUS;
Binary: simple protocol defined by Us, whose functions are described in the document "Simple
Protocol" downloadable at www.adfweb.com/download/filefold/Simple_Protocol_ENG.pdf;
ASCII: simple protocol defined by Us, whose functions are described in the document "Simple
Protocol" downloadable at www.adfweb.com/download/filefold/Simple_Protocol_ENG.pdf.
ADFweb.com S.r.l.
User Manual Modbus Master / Ethernet
Document code: MN67506_ENG
Revision 1.012
Figure 4: "Set Communication" window
Page 9 of 18