- ページ 2

コントローラー AVR SX440のPDF 操作マニュアルをオンラインで閲覧またはダウンロードできます。AVR SX440 4 ページ。 Generator automatic voltage regulator

AVR SX440 操作マニュアル
1. SPECIFICATION
Sensing Input
Voltage
190 ~ 264 VAC, 1 phase 2 wire
Frequency
50 / 60 Hz, selectable
Output
Voltage
Max. 90 VDC @ 207 VAC
Current
Continuous 4A
Intermittent 10A for 10 sec.
Resistance
Min. 15 ohm
Voltage Regulation
< ± 1% ( with 4% engine governing )
Voltage Build-up
Residual voltage at AVR terminal > 5 VAC
Thermal Drift
°
0.05% per
C change in AVR ambient
External Volts Adjustment
±8% with 1K ohm 1 watt trimmer
Unit Power Dissipation
Max. 12 watt
2. WIRING
1. K1, K2 : Field input external switch terminals.
Linked for normal operation.
2. P2, P3 : External power input terminals.
3. 3, 2 : Sensing input terminals.
4. 1, 2 : External VR terminals. Linked for useless.
5. X,XX : X connect to field (+), XX connect to field (-).
6. S1, S2 : Droop CT input terminal.
7. A1, A2 : VAR/PF controller input.
8. A, B, C : Link A, C for under 90KW.
Link B, C for 90 ~ 550KW.
Link A, B for over 550KW.
9. J1~J8 : Jump select terminals, 2-3,4-5,6-7. please
refer to Figure 2 and Figure 3.
______________________________________________________________________________________
2
All manuals and user guides at all-guides.com
Under Frequency Protection (Factory Setting)
Soft Start Ramp Time
Analogue Input
Quadrature Droop Input
Dimensions
Weight
3. ADJUSTMENT
3.1 Voltage Adjustment
The generator output voltage can be altered by
adjustment of the volt VR on the AVR board, or by
the external trimmer (1KΩ) if fitted.
1. The terminals 1&2 must be linked if no hand
2. Before start the generator, please turn the Volt
3. Turn the stability trimmer on the AVR board to
4. Connect a voltmeter to generator output voltage
5. Start generator set and run on no load at nominal
6. If the red Led is illuminated, refer to the under
7. Carefully turn volt trimmer clockwise until rated
Set point 95% Hz
Slope 170% down to 30 Hz
2 sec.
Sensitivity
1V for 5% generator volts
Input Resistance
1K ohm
Max. Input
± 5 VDC
Burden
10 ohm
Max sensitivity
0.07 A for 5% droop (PF=0)
Max. input
0.33 A
150mm L * 135mm W * 40mm H
418g ± 2%
trimmer.
trimmer on the AVR board fully anticlockwise
Turn the external trimmer to midway position.
midway position.
terminals.
frequency 50 ~ 53Hz or 60~63Hz.
frequency roll off adjustment.
voltage is reached.
SX440