コントロールユニット Allmatic BAXS900のPDF マニュアルをオンラインで閲覧またはダウンロードできます。Allmatic BAXS900 13 ページ。 For rolling shutters
Type of activation control
Dead man mode
Radio transmitter and visible closing system
Radio transmitter and closing system not visible
Automatic control (e.g. timed closure)
Table 1 - Minimum level of protection to be considered according to UNI EN12453
Protection A
The closure is activated by the dead man command, that is holding to move (hold-to-run)
Protection B
The closure is activated by the dead man command, through a key selector or similar device to prevent unau-
thorized use
Protection C
Limitation of the forces generated by the shutter / door / gate
Protection D
Devices, such as photocells, to detect the presence of persons or obstacles
Protection E
Sensitive devices, such as non-material barriers, to detect the presence of a person
11. AUTOTEST
BAXS900 is designed according to safety standards, and the same include some tests before movement. During these tests BAXS900
activates the "SAFETY CHECK" led on the front panel and performs a series of flashes on the courtesy light. This condition informs
the user of the next automation movement.
WARNING! The AUTOTEST procedure slightly delays movement but is NECESSARY for user safety.
WARNING! The courtesy light also acts as a motion detector, so if you have a device without the built-in courtesy light, you need to
install a light connected to the COURTESY LIGHT output, placing it visibly from the areas of movement.
12. PRESA RJ11 PER MODALITA' UPS
The UPS mode allows to give a consent to a UPS (Uninterruptible Power Supply) in case of blackout.
- Connect 230Vac UPS output to network input L, N and GND of the control unit BAXS900, see 230Vac terminal block (Pag. 2).
- Connect the UPS to a 13A socket.
- Connect the RJ11 control cable to the socket on the BAXS900 and the other end to the RJ11 input socket on the back of the UPS.
WARNING! DO NOT set "Infinite working time" (DIP 3 = ON) when using UPS mode.
WARNING! The autonomy and functionality of the UPS depends on the technical characteristics of the UPS itself. Keep UPS instruc-
tions handy if used. Allmatic does not provide UPS.
6-1622623 rev. 3
Use of the closing system
Group 1
Group 2
Qualified
Qualified
persons. (use in
persons. (use in
private area)
public area)
A
C or E
C or E
C or E
C and D, or E
C and D, or E
C and D, or E
Group 3
Unqualified
persons. (public
and private area)
B
Not possible
C and D, or E
C and D, or E
C and D, or E
9 / 12