Duct Length
The inlet and outlet duct length should be approximately
two to three wheel diameters long before and after the
fan to achieve cataloged performance.
Side Discharge
Make sure discharge is orientated in the same direction
as originally ordered, performance will change with
different discharge positions. Refer to Fig. 5 for proper
side discharge definition. Refer to the CAPS program or
consult factory for performance corrections.
Troubleshooting
Problem
Reduced
Airflow
excessive Noise
or Vibration
NOTE: Before taking any corrective action, make certain unit is not capable of operation during repairs.
NOTe
Before taking any corrective action, make certain unit is not capable of operation during repairs.
Replacement Parts
WHEEL
VENTURI
NOTe
Each fan bears a manufacturer's nameplate with model number and serial number embossed. These numbers will assist
the local Accurex representative and the factory in providing service and replacement parts.
Accurex warrants this equipment to be free from defects in
material and workmanship for a period of one year from the date of
purchase. Any units or parts which prove to be defective during the
warranty period will be replaced at our option when returned to our
factory, transportation prepaid. Motors are warranted by the motor
manufacturer for a period of one year. Should motors furnished by
Accurex prove defective during this period, they should be returned
to the nearest authorized motor service station. Accurex will not be
responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Accurex
reserves the right to change specifications without notice.
Cause
System resistance too high
Unit running backwards
Excessive dirt buildup on wheel
Improper wheel alignment
Wheel improperly aligned and rubbing
Foreign objects in wheel or housing
Unbalance of wheel caused by excessive dirt and
grease build up
MOTOR
COVER
HOUSING
Warranty
Left Side
Discharge
Inlet
Fig. 5
Corrective Action
Check system for proper operation of backdraft or
control dampers, obstruction in ductwork, etc.
Correct as shown in Fig. 4
Clean wheel
See Fig. 3 and Pre-Starting Checks
See Fig. 3 and Pre-Starting Checks
Remove objects, check for damage
Remove build up
VENTURI
MOTOR
PANEL
ACCESS
PANEL
MOTOR
Side Discharge
Duct Openings
Inline
Discharge
Unit Size
60-75
80-95
100
Height
120
130
140
Width
Right Side
160
Discharge
All dimensions are in inches.
WHEEL
ACCESS
PANEL
MOTOR
COVER
P.O. Box 410 Schofield, WI 54476
Phone: 800.333.1400 Fax: 715.241.6191
www.accurex-systems.com
IOM XID Rev. 1 June 2007
Copyright © 2007 Accurex, LLC
Width
Height
9
⁄
8
⁄
7
7
8
8
12
⁄
11
⁄
7
7
8
8
13
⁄
13
⁄
7
7
8
8
15
⁄
15
⁄
7
7
8
8
17
⁄
17
⁄
7
7
8
8
19
⁄
19
⁄
7
7
8
8
22
⁄
22
⁄
7
7
8
8