LRC MODEL
3.2
Pump and Piping
A. Regarding the piping illustration for cooling tower, please refer to the following chart:
B. When doing the piping work, diameter and length of the inlet pipe rigged on the two sides of
the hot water basin should be matched accordingly. Flow Control valves should be installed.
C. The pipe diameter should also match the water flow of tower design.
AMCOT COOLING TOWER CORPORATION OPERATIONS AND MAINTAINENCE MANUAL IS
OWNED BY LIANG CHI (USA) CORPORATION. THE NAME "AMCOT" AND AMCOT PRODUCT
LOGO ARE TRADEMARKS AND ANY REPRODUCTION WITHOUT WRITTEN CONSENT WILL
BE A VIOLATION OF LAW AND SUBJECT TO LEGAL ACTIONS. ALL RIGHTS RESERVED, 1998.
80 ~ 125
150 ~ 200
225 ~ 350
400 ~ 600
700 ~ 800
900 ~ 1250
DISTANCE FROM STRUCTURES (i.e.,
Buildings, etc..)
More Then 6.5 Feet
More Then 8 Feet
More then 9.5 Feet
More Then 10.5 Feet
More Then 13 Feet
More Then 16.5 Feet