6 Operation

After the device is powered on the operating mode is activated. The type of the signal can be
selected in the parameter in.t "Input signal". The complete list of the programming
parameters is shown in Table 7.2.
The input signal is digitalised, the square root calculated (if the function is enabled), the
signal scaled and displayed. The scale factor is calculated based on the parameter di.Lo
"Lower measuring limit" and di.Hi "Upper measuring limit". The display decimal point can be
specified in the parameters di.P.
For other signal processing functions see sections 6.1...6.3. For displayed errors see Table
6.1.
6.1

Control

ON/OFF control is implemented with the NPN transistor output (see 5.1.2). The parameters
SP.Lo "Lower setpoint limit" and SP.Hi "Upper setpoint limit" specify the control limits. The
control function can be selected in the parameter Cnt:
Heating
Cooling
Alarm within limits
Alarm outside limits
The safe output state can be selected in the parameter out.E.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·
DO-
K
DO+
VD
Fig. 5.4 NPN transistor output
Fig. 6.1
_
U
+
U
www.akytec.de