Douglas Lighting Controls WORXID2-DPR-L 설치 매뉴얼 - 페이지 2
{카테고리_이름} Douglas Lighting Controls WORXID2-DPR-L에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Douglas Lighting Controls WORXID2-DPR-L 2 페이지. Diversa occupancy & vacancy sensors - recessed ceiling, passive infrared (pir), 24vac
Installation Guide
General Programming Instructions
This covers mode programming using the onboard DIP and Dial switches.
Factory Defaults
All DIP switches in DOWN position. Time delay: 10 minutes; Natural Daylight level: 50% (200 lux).
***NOTE***
Diversa Occupancy Sensors with a "P" in the model number contain a Photo Sensor that is
controlled by DIP 6. The factory default for Natural Daylight Mode = ENABLED (DIP 6 DOWN).
This mode disables the Manual Override Button. To test sensor functionality, you may need
to disable Natural Daylight Mode (DIP 6 UP) to test sensor functionality.
• Start with the PIR Sensitivity at Medium (DIP 5 DOWN)
• To set the light level at which you want to prevent the sensor from turning light ON, rotate Light Level
Dial to adjust the light level
• To enable Restroom Mode , ensure that DIP 8 is UP. In this mode Pole 2 will remain on 50%
longer than Pole 1 (time is set with the Time Dial) and Pole 2 cannot be Photo Inhibited
DIP Switches & Dial Settings
Some DIP Switches C ontrol Optional Features Not Found on All Products
DIP #
Function
UP
1
PIR LED
Disabled
Walk-Through
2
Enabled
Mode
Manual Override
3
Disabled
4
Sensor Mode
Manual ON (Vacancy)
Auto ON (Occupancy)
5
PIR Sensitivity
High
Natural Daylight
6
Disabled
Mode ("P" models)
Light Level Mode
Light Level Dial
7
("DP" models)
Sets Photo Sensor
Sets Dimming Level
Restroom Mode
8
O set
(2-pole models)
Factory DIP & Dial Settings
UP
DOWN
1
2
3
4
5
Light Level Dial
Time Delay Dial
Photo Sensor "P" models only
5
1
Lo
Hi
TEST
Diversa by Douglas Lighting Controls
Diversa Occupancy & Vacancy Sensors - Recessed Ceiling, Passive Infrared (PIR), 24Vac
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
DIP Switch Modes
DIP 1 - PIR Detection LED
LED in Sensor's PIR window flashes GREEN when PIR detects motion. LEDs can be turned OFF with DIP switch. Sensor
continues to function.
DIP 2 - Walk-Through Mode
When Enabled and Occupancy switches lights to ON and sensor does not detect motion after 30 seconds of light ON,
an OFF Time Delay of 3 minutes is used (OFF Time Delay must be greater than 3 minutes). If motion is detected after
30 seconds of lights ON, the configured OFF Time Delay is followed.
DIP 3 - Manual Override
Manual Override Button can be disabled with DIP switch to prevent manual ON/OFF.
DIP 4 - Sensor Mode
Vacancy Mode - Lights must be turned ON manually when entering a room and are automatically turned OFF when
occupancy no longer detected. Maximizes energy s avings because lights are only turned on when lighting is
required.
Occupancy Mode - Automatically turns lights ON when occupancy is detected in a room and automatically turns
lights OFF when occupancy is no longer detected. This is a very convenient mode as lighting controls never have to
be touched. Because lights are always turned on when Occupancy is detected regardless of the need for lighting,
this is less energy efficient than Vacancy Mode.
DIP 5 - PIR Sensitivity
Can be moved from Medium sensitivity (default) to High sensitivity if sensor is not recognizing Occupancy.
DOWN
Default
DIP 6 - Natural Daylight Mode ("P" models)
Enabled
DOWN
When ENABLED, lights ON when Occupancy detected AND daylight level is below Light Level Dial setting. With lights
ON, an increase in daylight above the Light Level Dial setting will not force lights OFF.
Disabled
DOWN
DIP 7 - Light Level Mode ("DP" models)
This mode allows the light function to be set and controlled to support Natural Daylight Mode and Closed Loop
dimming. WIth DIP UP the light level dial is used for setting the light level for Natural Daylight Mode. With DIP DOWN,
DOWN
Enabled
the light level dial is used for setting Closed Loop Dimming.
DIP 8 - Restroom Mode (2-pole models)
DOWN
Pole 1 and Pole 2 are set to synchronize to the same Photo and Time Delay settings. With Restroom Mode = Offset,
Pole 2 will activate at the same moment as Pole 1 when Occupancy detected; however, Pole 2 will be offset so that
Medium
DOWN
OFF delayed 50% longer than Pole 1. (e.g. Light is Pole 1 and Fan is Pole 2. Fan would stay ON 50% longer than light).
Auto Time Mode
DOWN
Enabled
Activated when Time Delay Dial is set to Auto Time. Red LED indicator will be ON. In this mode, time delay will start
automatically set by the sensor learning occupancy patterns.
Light Level Dial
DOWN
Test Mode
Activated when Time Delay Dial is set to TEST. Test Mode LED will flash red for 5 minutes, providing a short Time Delay
when testing the installation to determine if the sensor is working as intended or requires adjustments. After 5
Synchronized
DOWN
minutes, LED will stop flashing and Time Delay reverts to Factory Time Delay setting (10 minutes).
6
7
8
Test Mode LED
10
20
30
(=LED ON)
Auto Time
www.douglaslightingcontrols.com
Troubleshooting
Before calling Technical Support, please review the following Troubleshooting Guide.
Issue
Possible Cause
Recommended Solution
Sensor is set to Manual ON Mode.
Check DIP 4. Move DOWN for Auto ON.
This only applies to Photo Sensor ("P") models. Check DIP
6. If DOWN, sensor is in Natural Daylight Mode, therefore
lights will only turn ON if there is insufficient natural
Sensor is set to Natural Daylight Mode (Photo
daylight. Rotate the Light Level Dial clockwise pressing
Inhibit) and Sufficient Natural Light is Present.
the Manual Override Button until the Lights turn ON.
Natural Daylight mode can be disabled by moving DIP 6
UP.
Lights will not turn
ON automatically
Manual Override Button was used to turn lights
Wait for OFF Time Delay to count down, then with
OFF.
motion detected lights will turn ON. Manual Override
Button can be disabled by moving DIP 3 UP.
Check the wiring diagram. Ensure ground is connected.
With DIP 1 DOWN, check for motion detection by waving
Power
has
been
interrupted
or
wiring
hand in front of sensor lens. Activation LED will blinnk
connection is intermittent.
green.
This only applies to Photo Sensor "P" models. Check DIP 6.
If DOWN, sensor is in Natural Daylight Mode; therefore,
lights will only turn ON if there is insufficient natural
Sensor is set to Natural Daylight Mode (Photo
daylight. Rotate the Light Level Dial clockwise pressing
Inhibit) and Sufficient Natural Light is present.
Lights will not turn
the Manual Override Button until the lights turn ON.
ON Manually
Natural Daylight mode can be disabled by moving DIP 6
UP.
Check the wiring diagram. Ensure ground is connected.
With DIP 1 DOWN, check for motion detection by waving
Power
has
been
interrupted
or
wiring
hand in front of sensor lens. Activation LED will blinnk
connection is intermittent.
green.
If the Sensor is in AUTO Mode, it may take longer than
expected to turn the lights off. Set the Time Delay to 5
Sensor is in Auto Time Mode.
minutes and leave space to determine if the Sensor is
Lights will not turn
functioining. The maximum Time Delay is 30 minutes.
OFF automatically
Sensor may be detecting heat from HVAC registers or
other heat sources. Check Installation location for heat
Sensor is being activated by a heat source other
than occupant.
source. Reduce PIR sensitivity by moving DIP 5 DOWN.
Move sensor location – see guidelines.
Lights will not turn
Move DIP 3 DOWN to enable Manual Override Button.
OFF Manually
Manual Override Button has been disabled.
14040200-B