Configuration
There is no USB or Bluetooth connector on this product. The configuration is done at the factory and can only be
changed via Downlink, i.e., from the customer's platform.
•
In LoRaWAN, downlinks can be received by the product after each frame sending.
•
In Sigfox, they can be received only when sending life frames.
The Downlink configuration frames are explained below, depending on the setting you wish to change.
Parameter code (1 byte)
0x03
Parameter code (1 byte)
0x0A
Frequency of emission of the keep alive frame
Parameter value (1 byte)
The possible values are:
0x04 = every 10 minutes
0x05 = every hour
0x0A = every 2 hours
0x0B = every 4 hours
0x0C = every 8 hours
0x06 or 0x09 = once a day (factory setting)
0x0D = every 2 days
0x0E = every 3 days
0x0F = every 4 days
0x07 = every 7 days
0x08 = every 30 days
Operating mode
Parameter value (1 byte)
The possible values are:
0x00 = standard counter mode with transmission every 10 minutes
0x01 = standard counter mode with transmission every 6 hours
0x02 = standard counter mode with transmission every hour (factory setting)
0x03 = standard counter mode with transmission every 3 hours
0x04 = standard counter mode with transmission every 30 minutes
0x05 = standard counter mode with transmission every 12 hours
0x06 = standard counter mode with transmission every 24 hours
0x07 = standard counter mode with transmission every 48 hours
0x09 = change of state detection mode with radio transmission on falling edge
0x0A = change of state detection mode with radio transmission on rising edge
0x0B = detection mode change of state with radio transmission on falling and rising edges
0x0C = ECO counter mode with reading every 10 minutes + transmission once an hour
0x0D = ECO counter mode with reading every 30 minutes + transmission every 3 hours
0x0E = ECO counter mode with reading once an hour + transmission every 6 hours