GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
OPTION #1 MOMENTARY START CONTACT - TYPICAL GENERATOR W/ STARTER CONTROL BOX
The GSCM-mini-D option #1 provides the same momentary glow plug operation for those 3 wire diesel applications where the key switch
or off button is pressed for 10 seconds energizing the glow plugs, then the start button is pressed starting the generator. The GSCM-
mini-D energizes K2 for 10 seconds to heat the glow plugs, then energizes K1 relay, providing a signal to the start/crank input and
removes it when the generator has reached 45Hz, or half speed. The K2 relay also provides a momentary "stop" signal until the
generator AC Hz has dropped to zero. For operational sequence details see Page 4, Section - 1
OPTION #2 MAINTAINED START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL BOX
The K1 relay provides a continuous run signal for generators
requiring a "maintained" start signal. The K2 relay provides a
momentary "stop" signal until the generator AC Hz has
dropped to zero. For GSCM-mini-D operational sequence
details see Page 4, Section - 2
OPTION #3 IGNITION KEY SWITCH TYPE START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL
The K1 relay is used to switch the starter input that is looking
for a momentary signal and opens it when the AC line output
has reached 45Hz. The K2 relay provides a continuous run
signal for generators requiring a "maintained" ignition signal.
When the GSCM-mini-D no longer receives a run command,
K2 relay opens telling the generator to shutdown. For GSCM-
mini-D operational sequence details see Page 5, Section - 3
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
A double pole "kill switch" wired and installed by the user, stops
the generator instantly in emergency situations such as a fuel
spill. One switch pole (N.C.) kills power to the GSCM-mini-D
opening all relays. The other switch pole (N.O.) shorts out the
magneto for an instant stop.
A single pole "kill switch" wired and installed by the user, stops
the generator instantly in emergency situations such as a fuel
spill. One switch pole (N.C.) kills power to the GSCM-mini-D
opening all relays shutting down the ignition switch type
generators.