{카테고리_이름} Andover Controls EMX34/CK34에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Andover Controls EMX34/CK34 12 페이지. Cardkey interface board
Wiring the Cardkey Reader to the EMX 34 Interface Board
Each Cardkey input on the EMX34 takes 6 wires. There are four inputs, located along the
right-hand side of the printed circuit board (P2, P4, P6, and P8).
1. Locate the existing gray cable on the back side of the Cardkey reader. Strip the end
of the cable to expose the wires.
2. Strip the ends of the black, white and red wires.
3. Following the wiring diagram below, place the appropriate wires into the correct
terminals and tighten the screws. Insert the shield into the GND terminal.
Wiring the EMX 34 to the Cardkey Reader and LEDs
EMX 34 PCB
(6)
(5)
P2
(4)
(3)
(2)
(1)
Technical Manuals Online! - http://www.tech-man.com
5VDC
LED
PWR
Black
RED
Red
LED
White
GREEN
Shield
LED
DATA
GND
5VDC
existing cable (for reader)
LED
PWR
RED
extra cable (for LEDs)
Cardkey Reader
Red
White
Black
Shield
Molex
Connector
EMX 34 Installation Guide
9