1.3.4 Automatic restart after voltage failure
Warning
If activated and provided the module was in the
automatic operation mode, the compressor will
automatically restart if the supply voltage to the
module is restored within a programmed time
period.
The power recovery time (the period within which
the voltage must be restored to have an automatic
restart) can be set between 1 and 255 seconds or
to Infinite. If the power recovery time is set to
Infinite, the compressor will always restart after
a voltage failure, no matter how long it takes to
restore the voltage. A restart delay can also be
programmed, allowing e.g. two compressors to be
restarted one after the other.
1.3.5 Permissive start
2920 1475 00
1.4 Control panel
1.4.1 LEDs/buttons/keys
Ref.
Designation
Function