Installation
Removing the Grille
The grille is secured to the loudspeaker by the grille lock. Disengage the grille lock by inserting a small tool through the grille perforation
(no larger than 1.5 millimeters in diameter). While depressing the grille lock, slide the grille away from the loudspeaker to detach it.
Note: The grille lock is located on the loudspeaker opposite of the tap switch. See the diagram below for the grille lock location.
Tap switch
Adjusting the Logo
The FreeSpace FS4SE comes with a pre-installed Bose logo for horizontal installations. The loudspeaker also comes with a separate logo
for vertical installations. To remove the logo, peal it away from the loudspeaker grille. To apply the vertical logo, find the center of the
grille and align the notches on the back of the logo with the grille perforation. Press to affix it to the loudspeaker grille.
Safety and Regulatory Compliance
The Bose FreeSpace FS4SE loudspeaker has passed testing and complies with the following specifications and uses:
Listed to ANSI/UL 1480-2016, CAN/ULC-S541
Fire Protective Signaling Use – UL Category UUMW/UUMW7, File Number S 3241. Control Number 42S9.
Not for use with DC-supervised systems.
Suitable for use outdoors in wet locations.
EN 54-24: 2008, Loudspeaker for Voice Alarm Systems for Fire Detection and Fire Alarm Systems for Buildings
Environmental: Type B (outdoor applications)
Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 640.
Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 760.
NFPA 70, National Electric Code, 2002, Article 300-22 (c).
NFPA 90-A, 2002, Installation of Air Conditioning and Ventilation Systems, Paragraph 4.3.10.2.6.5.
EMC Directive 89/336/EEC and Article 10 (1) of the directive, EN50081-1 and EN50082-1 as signified by the CE mark.
The Bose FreeSpace FS4SE has been designed to the requirements defined in the following European regulatory specifications for combination systems:
British Standard Code of Practice BS 5839, Part 8, when used with the ceramic terminal block and thermal fuse.
Tested to IEC60268-5.
Nominal Coverage Angle (per UL 1480) Vertical: 115°/65° at –3 dB; 145°/40° at –6 dB
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):
Wattage
CAN/ULC-S541
Canada
Tap
70 V
2.5 W
85.6 dBA
5 W
88.2 dBA
88.4 dBA
10 W
91.1 dBA
90.8 dBA
20 W
93.8 dBA
93.4 dBA
40 W
96.2 dBA
96.1 dBA
8 Ω
95.3 dBA
SPLs given are per the UL 1480 specified reporting method.
Frequency response:
Fire alarm (UL): 80 Hz to 17000 Hz
8 • English
Horizontal: 120°/60° at –3 dB; 145°/35° at –6 dB
Wattage
100 V
Tap
—
2.5 W
5 W
10 W
20 W
40 W
—
8 Ω
ANSI/UL 1480-2016
United States
70 V
100 V
79.3 dBA
—
81.9 dBA
82.3 dBA
84.8 dBA
84.8 dBA
87.6 dBA
87.6 dBA
90.1 dBA
90.2 dBA
90.3 dBA
—
2531
Bose Corporation
100 The Mountain Rd, Framingham, MA 01701
20
DOP 434849-10
EN 54-24: 2008
Loudspeaker for voice alarm systems for fire detection and fire
alarm systems for buildings
FreeSpace FS4SE
Provided options:
Type B
For DOP 434849-10, see pro.Bose.com/FS4SEDOP_UK
FreeSpace FS4SE • Installation Guide
PRO.BOSE.COM