Aube Technologies CT280-3H3C 설치 매뉴얼 - 페이지 3
{카테고리_이름} Aube Technologies CT280-3H3C에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Aube Technologies CT280-3H3C 17 페이지. Programmable h/c controller
4. Principles of Operation
4.1
Automatic Heating/Cooling Changeover
With automatic heating/cooling mode changeover, there's no need to adjust
the controller at every change of season or weather condition. The controller
switches automatically between heating mode and cooling mode to maintain
the desired temperature.
Manual Mode
When the controller is in manual mode, the heating/cooling mode
changeover occurs as follows:
• The controller switches to cooling mode when the indoor
temperature is higher than the setpoint by more than 1.5°C (2.5°F)
for 15 minutes.
• The controller switches to heating mode when the indoor
temperature is lower than the setpoint by more than 1.5°C (2.5°F) for
15 minutes.
Automatic Mode
When the controller is in automatic mode, it follows the programmed
schedule. Two temperature settings (heating setpoint and cooling setpoint)
are programmed for each period of the schedule. The heating/cooling mode
changeover occurs as follows:
• When the controller is in heating mode, the indoor temperature is
maintained at the heating setpoint. However, if the temperature rises
and remains above the cooling setpoint for 15 minutes, the controller
will switch to cooling mode.
• When the controller is in cooling mode, the indoor temperature is
maintained at the cooling setpoint. However, if the temperature drops
and remains below the heating setpoint for 15 minutes, the controller
will switch to heating mode.
4.2
Balance Points (heat pumps only)
Balance Points are used to disable the heat pump or the auxiliary heating
when the outdoor temperature is below or above a set temperature.
• When the outdoor temperature is below the Balance Point Low
(bPL), the heat pump is disabled and only auxiliary heating can be
used (see page 8, item 5).
• When the outdoor temperature is above the Balance Point High
(bP H), the auxiliary heat is disabled and only the heat pump can be
used (see page 8, item 6).
NOTE: Balance Points cannot be used if the AC144-03 outdoor temperature
sensor is not connected to the controller.
4.3
Heating During Defrost (heat pumps only)
The auxiliary heat is activated during defrost except under the following
conditions:
• When the outdoor temperature is above the defrost point (see
page 8, item 7).
NOTE: This condition will not apply if the AC144-03
outdoor sensor is not connected to the controller.
• When the plenum temperature is above 40°C (104°F) for add-on
installations only. The auxiliary heat is re-activated when the plenum
temperature drops below 32°C (90°F).
apply if the AC146-410 plenum sensor is not connected to the
controller.
NOTE: The auxiliary heat's short-cycle protection is disabled during defrost.
4.4
Types of Heat Pump Installations
The controller can be configured for either of the following types of heat
pump installations (see page 8, item 8).
• Add-on Installation: This type of installation is performed when
adding a heat pump to an existing furnace. When the heat pump is
installed, the furnace becomes the auxiliary heat source. In this type
of installation, the indoor coils are usually installed downstream of
TH146-P-U
NOTE: This condition will not
the auxiliary heat source. When the controller is configured for an
add-on installation, the heat pump is disabled during auxiliary
heating to prevent overpressure.
• New Installation: In this type of installation, as there is not already a
furnace, the auxiliary heat source is installed at the same time as the
heat pump. In this type of installation, the indoor coils are located
upstream of the auxiliary heat. When the controller is configured for
a new installation, the heat pump and the auxiliary heat can operate
simultaneously.
4.5
Interstage Delay
Interstage Delay is the time allocated for the temperature to return to an
acceptable value when it deviates too far from the setpoint. If this time has
elapsed, the next heating or cooling stage is activated. The heating or
cooling stage will be deactivated when the temperature returns to an
acceptable value. The Interstage Delay is fixed at 4 minutes if the controller
is configured for an HVAC system and is user-adjustable if it is configured for
a heat pump (see page 8, item 9).
4.6
Low and High Temperature Limits
Low Temperature Limit (LLMT) and High Temperature Limit (HLMT) are
used to keep the plenum from becoming too cold or too hot. During cooling,
if the plenum temperature is lower than LLMT, a cooling stage is deactivated
starting with the one that was last activated. If, after a while, the temperature
is still too low, another cooling stage is deactivated and so on. Likewise,
during heating, if the plenum temperature is higher than HLMT, a heating
stage is deactivated starting with the one that was last activated. If, after a
while, the temperature is still too high, another heating stage is deactivated
and so on. (see page 8, items 10 and 11.)
WARNING: LLMT and HLMT can be used in parallel with an UL353-
approved device but they do not replace such device.
NOTE: LLMT and HLMT cannot be used if the plenum temperature sensor is
not connected to the controller.
4.7
Smart Fan
When Smart Fan is enabled (see page 8, item 15), the fan operates as
follows:
• During periods 2 and 4 of automatic mode and during the
unoccupied mode (i.e., when you are sleeping or away from home),
the fan operates only when heating or cooling is activated.
• The fan operates continuously the rest of the time.
NOTE: For Smart Fan to work, set the fan to On (see user guide).
4.8
Automatic Humidification / Dehumidification Changeover
If a humidifier and a dehumidifier are both connected to the controller, the
controller will automatically switch between the two devices to maintain the
desired humidity level. The changeover occurs when the humidity deviates
from the setpoint by more than 3% for 30 minutes.
4.9
Dehumidification by Droop
Dehumidification by droop is a method of dehumidification without using a
dehumidifier. This method is possible only if your system has a cooling
stage. When this feature is enabled (see page 8, item 18), if the humidity
level is too high, the temperature is temporarily lowered below the setpoint to
reduce the indoor humidity level.
NOTE: Dehumidification by droop can cause overcooling.
4.10
Dehumidification by Air Exchanger
Dehumidification using an air exchanger will not be efficient if the outdoor
temperature is too high. When an air exchanger is used, the controller will
disable dehumidification if the outdoor temperature is NOT lower than the
indoor temperature by more than 5°C (9°F). When this occurs, the message
HIGH TEMP is displayed.
3/8