Aube Technologies TH132 AF 소유자 매뉴얼 - 페이지 3
{카테고리_이름} Aube Technologies TH132 AF에 대한 소유자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Aube Technologies TH132 AF 3 페이지. Control module
Aube Technologies TH132 AF에 대해서도 마찬가지입니다: 소유자 매뉴얼 (3 페이지)
The PB130-230 power base is used to power a TH13x Series control
module. The resistive load must not exceed 3450 watts (NI) @
230 VAC (15 A).
Parts
One (1) PB130-230 power base
One (1) floor sensor (for AF and F control modules only)
One (1) wall plate (optional, in certain countries)
Guidelines
Turn off power to the heating system at the main power panel to avoid
electrical shock. Installation should be carried out by an electrician.
All work must conform to the applicable country standards for
electrical installations and wiring.
This thermostat should be connected on a circuit equipped with
a fuse or a circuit breaker. It must be installed on a certified
electrical box.
For a new installation, choose a location about 1.5 m above the
floor.
For electric baseboards, convectors and fan-forced heaters, the
thermostat must be installed facing the heating system.
The thermostat must be installed on an inside wall.
Avoid locations where there are air drafts (top of staircase, air
outlet), dead air spots (behind a door), direct sunlight or
concealed chimneys or stove pipes.
Technical Specifications
Model: PB130A-230
Supply: 230 VAC, 50 Hz
Load: 15 A maximum (resistive only)
Power: 3450 Watts (NI) @ 230 VAC
Conformity: EN60730-2-9 / EN50081-1 / EN50082-2
Storage: -20°C to 50°C
Protection: Class 2
Protection
degree: IP21
Automatic
action: Type 1.B
Environment: Normally polluted
Size (H • W • D)
: 2.95 x 2.95 x 0.55 in. (75 x 75 x 14 mm)
NOTE:
The terminals are designed to handle a cross-section of wire
2
measuring 0.33 to 3.1 mm
.
Procedure
Remove the screw holding the
control module to the power base
and lift the lower part upwards.
The screw cannot be completely
removed.
PB130
Before making the connections, make sure
that the base covers the electrical box
entirely. If not, install a wall plate at the
back of the base as shown.
1.
Connect the wires:
• Power:
Terminals 1 & 5
2.
• Load:
Terminals 2 & 4
see note 1
•
Pilot
Wire:
Terminal 3
see note 2
•
Floor
sensor:
Terminals 6 & 7
(no polarity)
see note 3
Note 1
If a contactor is used between the thermostat and the load,
install a snubber at the contactor's coil terminal to ensure
the proper operation of the thermostat.
Note 2
This connection is required on some models only.
3.
Note 3
For the proper operation of the thermostat, the floor sensor
must be centered between two heater wires having a
maximum temperature of 80°C. The floor sensor wire must
not cross any heater wire or be placed close to it.
Push wires into the electrical box and
secure the base to the electrical box
anchorage. The head of the screw
must be less than 2 mm thick.
BEFORE installing the control
module onto the base, set the
configuration switches (if any)
on the control module
the user
guide).
4.
WARNING: This power base must be used
heating cycles. If your control module has a selector switch for
choosing the heating cycle, ensure that the switch is correctly set.
Return power to the heating system.
PB130
Installation Instructions
230 V Line Voltage Power Base
(refer to
only
with
400-130-001-E
19/9/05
15-minute
1/1