AuCom CSXI-045 사용자 설명서 - 페이지 6

{카테고리_이름} AuCom CSXI-045에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AuCom CSXI-045 13 페이지.

ADJUSTMENTS
Soft Stop Time
Excess Start Time
Auxiliary Relay Function
Phase Sequence Protection
NOTE
Auxiliary relay function and phase rotation are configured using a shared switch. Set the
auxiliary relay function as required, then set phase rotation protection.
Page 6
Select the soft stop ramp time (D).
Soft stop extends the time soft starter takes to
reduce voltage to zero.
The ramp time does not control the time the
motor will take to stop completely.
Configure the soft starter's excess start time
protection.
Select a time slightly longer than the motor
requires for a normal healthy start. The soft
starter will trip if the start does not complete
within the selected time (E).
Select the function of the soft starter's
programmable output (terminals 23, 24).
When set to "Run", the relay will operate when
the soft start is complete. When set to "Trip",
the relay will operate when the soft starter trips.
Configure the soft starter's phase sequence
protection.
Select the allowable phase sequences. A setting
of "Fwd" allows forward sequence (positive
rotation) only and a setting of "Any" defeats the
protection.
CSXi
Time
Time
Time
710-02408-00H