Anywire ASLINK BL296SB-04F-4A-20 제품 설명서 - 페이지 6

{카테고리_이름} Anywire ASLINK BL296SB-04F-4A-20에 대한 제품 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Anywire ASLINK BL296SB-04F-4A-20 15 페이지.

[Notes on Combined Use with 4-Wire (Isolated) Terminal]
If the total length of the sections where all the DP, DN, 24V, and 0V lines run in parallel in the power supply system is more than 50m, connect an
ASLINK lter (Type ANF-01) or a lter manufactured by COSEL Co., Ltd. (Type EAC-06-472) in series to the 24V and 0V lines at a position where
these four lines start running in parallel.
This will improve noise resistance, suppress the adverse effects of crosstalk caused by transmitted signals, and stabilize signals.
The above lters must be inserted regardless of whether power is supplied to all terminals collectively from the power supply for the master or
power is supplied to each terminal individually from their local power supply.
Insert the "ASLINK lter [Type ANF-01]" regardless of installation method and distance when complying with CE Standard.
■Filter allowable current
Product
ASLINK lter
Filter of COSEL Co., Ltd.
■AnyWire Type: ANF-01 Connection example
①Power supply to the entire system
AnyWireASLINK master
DP
POWER IN
DN
24V
0V
LG
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
② Local power supply/branching
AnyWireASLINK master
DP
POWER IN
DN
24V
0V
LG
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
Type
Allowable power current
ANF-01
MAX 5A/24V DC
EAC-06-472
MAX 6A/24V DC
SLAVE
24V
24V
0V
0V
PE
ANF-01
If the total length of the section where all the DP, DN, 24V, and 0V lines run in parallel is more than 50m
2-wire
4-wire
terminal
terminal
SLAVE
24V
24V
0V
0V
PE
ANF-01
If the total length of the
section where all the
DP, DN, 24V, and 0V
lines run in parallel is
more than 50m
-BL296*B04F*4A20 6/15-
2-wire
terminal
POWER IN
SLAVE
L
24V
24V
24V
N
0V
0V
0V
FG
PE
ANF-01
24V DC
stabilized
power supply
General-purpose power
supply lter
(Use it if necessary.)
2-wire
4-wire
terminal
terminal
4-wire
4-wire
terminal
terminal
A
4-wire
terminal
B
If the total length of the sections (A + B)
where all the DP, DN, 24V, and 0V lines
run in parallel is more than 50m
4-wire
terminal
DP
DN
BT0
4-wire
terminal
DP
DN
BT0
4-wire
terminal