{카테고리_이름} Automationdirect.com Productivity 2000 P2-08AD-2에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Automationdirect.com Productivity 2000 P2-08AD-2 8 페이지. Analog input
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
82mW
Enclosure Type
Open Equipment
UL508 File E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System or removable terminal block
Field Wiring
(not included). See "Wiring Options" on page 5.
See the "EU Directive" topic in the Productivity Suite
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type (not included) 18-position removable terminal block
Weight
90g (3.2 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com
Input Specifications
Input Channels
8
Module Signal Input Range
0-10 VDC
Signal Resolution
16-bit
Resolution Value of LSB
0-10 VDC = 152μV per count
(least significant bit)
(1 LSB = 1 count)
Data Range
0 to 65535 counts
Input Type
Single-ended (1 common)
Maximum Continuous Overload
±100V
Input Impedance
250kΩ (typical)
Hardware Filter Characteristics
Low Pass, -3dB @ 100Hz
7ms per channel
Sample Duration Time
(does not include ladder scan time)
All Channel Update Rate
80ms
Open Circuit Detection Time
Zero reading within 1s
Conversion Method
Successive approximation
Accuracy vs. Temperature
±25PPM / ºC maximum
0.1% of range
Maximum Inaccuracy
(including temperature drift)
±0.015% of range
Linearity Error (end to end)
Monotonic with no missing codes
Input Stability and Repeatability
±0.015% of range (after 10 min warmup)
Full Scale Calibration Error
±0.015% of range maximum
(not including offset)
Offset Calibration Error
±0.015% of range maximum
Max Crosstalk
-76dB, ±10 LSB
External DC Power Required
24VDC (-20% / +25%) 35mA
Tech Support 770-844-4200