Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
WHAT TO DO IN CASE OF FIRE
1. DON'T PANIC — escape may depend on clear thinking.
2. Get out of the house following the planned escape routes, if possible. Do
not stop to dress or to collect anything.
3. Open doors carefully only after feeling them to see if they are hot. If a door
is hot, do not open it— follow an alternate escape route.
4. Keep close to the floor — smoke and hot gases rise. Breathe through a
cloth (wet, if possible) and take short shallow breaths.
5. Keep doors and windows closed unless it is necessary to open them for
escape.
6. Meet at your meeting place after leaving your home.
7. Call the local fire department as soon as possible from outside
the home.
8. Never re-enter a burning building.
For more information about fire safety, contact your local fire department. They
can supply more detailed information about making your home as free from fire
hazards as possible and about planning for escape in case of fire.
MOUNTING
First, determine the best location for the smoke detector; a location that pro-
vides strong wireless transmission paths and proper smoke detection. A GOOD
TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED
MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE
DETECTOR. To check, perform the test described in the TESTING
TRANSMITTER SIGNAL section of this manual. To mount the detector:
1. Once a suitable location has been determined, install the mounting bracket
on the ceiling or on the wall (if local ordinances permit). Use the two screws
and anchors provided.
2. Prior to mounting the detector to the mounting bracket, the system must
"enroll" the detector's ID. See the PROGRAMMING section for the steps to
follow.
3. Turn the detector in a clockwise direction in the mounting bracket until it
clicks into place.
4. Test the detector immediately after completing the installation (as described
in the TESTING section of this manual) and refer to the control system's
instructions for additional information concerning the use of wireless smoke
detectors.
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
Figure 2. Detector Mounting Bracket
Figure 3. Mount Detector Across Ceiling Panel Support
AD300-00-00
CAUTION
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
ALIGNMENT
ARROWS
DO NOT attach the detector to removable ceiling panels. Attach the detector
across panel support as shown in Figure 3.
TAMPER PROTECTION
This detector has a built-in tamper switch that will cause a CHECK signal to
be displayed at the console of the detector if it is removed from its installation
bracket. The mounting bracket can also be made tamperproof by breaking off
the smaller tab at the scribed line (see Figure 2), thus preventing removal of
the detector without a tool. To remove the detector, use a small screwdriver to
depress the tamperproof tab and turn the detector counterclockwise.
TESTING
NOTE: Before testing, notify the proper authorities that the smoke detector
system is undergoing maintenance and will temporarily be out of ser-
vice. Disable the zone or system undergoing maintenance to prevent
unwanted alarms.
Detectors must be tested after installation and following periodic maintenance.
The 5808LST may be tested as follows:
A. TEST SWITCH
1. A recessed test switch is located on the detector housing.
2. Push and hold the recessed test switch for a minimum of 5 seconds.
Use a small screwdriver or allen key maximum diameter of .18" (The
alarm panel will trigger and then the smoke detector will go into alarm. If
the tool is removed from the recessed switch the sounder will shut off.)
3. The LED on the detector should blink once per second and the horn
should sound within 3 seconds.
B. SMOKE ENTRY TEST
Hold a smoldering punk stick or cotton wick at the side of the detector and
gently blow smoke through the detector until the unit alarms.
C. DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)
Direct the heat toward either side thermistor. Be sure to hold the heat
source about 12 inches from the detector to avoid damage to the plastic.
The detector will reset only after it has time to cool.
Smoke detection testing is recommended for verifying system protection
capability.
A detector that fails to activate with any of these tests should first be cleaned
as outlined in this manual's MAINTENANCE section. If the detector still fails to
activate, return for repair.
Notify the proper authorities that the system is back on line.
TESTING TRANSMITTER SIGNAL
NOTE: Remove battery tab before installation.
This test should be performed before installation to determine a strong com-
munication path with the control panel and after installation is complete. Also,
the owner/user should test the unit at least weekly.
1. Activate the wireless system's TEST mode from the console.
2. Depress and hold the smoke detector's TEST switch and the detector
S0158-00
should immediately transmit an alarm signal to the control panel. The built-
in horn will start to sound about 2.5 seconds after depressing the button.
3. The wireless system's console should emit at least 3 audible sounds
when the alarm transmission is received and will display the transmitting
detector's ID number.
4. When the console has received the test signal, release the TEST switch.
The horn will immediately stop and a few seconds later the detector's ID
number will clear from the console display.
5. If the console does not respond as noted, check the polarity of the batter-
ies and be sure they are fresh. If this is an initial installation, try moving
the detector to another location that provides proper reception. Also be
sure that the detector's ID has been "enrolled" by the control panel (see
PROGRAMMING). Then, repeat the test.
6. Turn off the system's TEST mode from the console (security code + OFF).
S0162-00
3
CAUTION
I56-918-14R