DYNAPAR HS35iQ 빠른 시작 매뉴얼 - 페이지 2
{카테고리_이름} DYNAPAR HS35iQ에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DYNAPAR HS35iQ 5 페이지.
White Paper
By Robert Cachro, Sr. R&D Engineer and Brad Stecker, Engineering Manager
Introduction
In this example the fault output from an HS35iQ encoder was connected to a Rockwell PLC. A simple single line
of ladder logic was used to read the fault line from the encoder and turn on an LED when a fault is present. The
LED is just an easy way to indicate the fault was successfully read from the encoder but other solutions such as
alerting maintenance are possible by utilizing the fault output function.
Hardware Setup
The following components were used to test this example:
•
HS35iQPROGR81721R2 encoder with 2.2k load resistors
•
L27ERM-QBFC1B PLC
•
24V DC Power supply
•
LED with current limiting resistor
The supply terminals for the PLC and the encoder were both connected to the same 24V DC power supply. The
24V power supply was also connected to the +V and COM0 connections on the "DC OUT" port included with the
PLC. The anode or positive side of the LED had a resistor connected in series to limit the current supplied from
the PLC output. The LED/resistor pair was connected to DC OUT 08 and COM. The fault output from the encoder
was connected to DC IN 00. COM0 of "DC IN" was also tied to common (COM) of the PLC and encoder. See
the wiring diagram in Figure 1.
DYNAPAR | Phone: 1.800.873.8731 | Website:
www.dynapar.com