Safety

2 Safety
2.1

Intended use

The RG 210 level controller may only be used as a level switch, as
level control for filling or as level control for emptying for liquids. The
RG 210 level controller detects minimum or maximum levels and
switches pumps or valves to control levels of liquids.
The RG 210 level controller consists of a control unit and one PTC
thermistor probe (level switch) or two PTC thermistor probes (level
control for filling and emptying). The control unit may only be used
with PTC thermistor probes type 937 and type 150.
The RG 210 level controller may only be used for the following
liquids:
With the type 937 PTC thermistor probe only for:
With the type 150 PTC thermistor probe only for:
and comparable liquids (not AI, AII !) with equivalent heat conductiv-
ity if these liquids do not attack the following wetted parts:
Any use other than the use explicitly stated in this instruction manual
is not permitted.
2.2

Predictable incorrect application

The RG 210 level controller must never be used in the following:
4
Fuel oil EL, L or M
Water
Fuel oil EL, L or M
Diesel fuel or low-viscosity lubricants group AIII and danger
class AIII
Motor oils, gearbox oils and hydraulic oils
Vegetable oils and transformer oils
Antifreeze agents
Oil-water mixtures, emulsion
PTC thermistor probe: stainless steel
Plastic: PA6 (Furkamid B SK 1)
Sealing material: 3M Scotch Cast No 815 perm. elast. 2 comp.
Cable Oilflex 100: resistant to acids, lye and oils and not agglu-
tinating or coking
Use as an overfill alarm system according to TRbF
RG 210