5.3.2. Drive Bushing

Standard drive bushings are ISO 5211 star. Verify
actuator drive bushing matches valve or actuator device
stem before mounting.
Actuator
Size
Drive
-690
17mm
-1350, 1700
19mm
-2640, 4400, 5200
27mm
-6900, 10500
36mm
-17500, 25900
36mm

Housing Cover

WARNING:
Flamepath surfaces on XE and XC actuators
must not be damaged in any way. DO NOT
FORCE cover onto actuator body.
Actuator housing covers are attached with bolts in each
corner. Unscrew bolts to remove cover.
Actuator
Size
-690
-1350, 1700
-2640, 4400, 5200
-6900, 10500
-17500, 25900
www.atcontrols.com
Std.
Size
Bolt Hex
Size
6mm
8mm
10mm
10mm
10mm

Limit Switch Setting

WARNING:
Hazardous voltage. Turn off all power and lock
out service panel before installing or modifying
any electrical wiring. Use caution when
energizing inputs.
CAUTION:
Setting limit switches incorrectly may result in
actuator stopping by the mechanical stops.
This may overheat the motor and force it into
thermal overload. Electrical operation will not
be possible until overload resets. The motor
may eventually fail if repeatedly overheated.
The motor control limit switches and auxiliary switches
have independently adjustable cams.
Switch order from top to bottom of the stack:
CLS = Close motor control
ACLS = Auxiliary close
OLS = Open motor control
AOLS = Auxiliary open.
CLS CAM
(Close Limit
Switch Cam)
OLS CAM
(Open Limit
Switch Cam)
9
WE/XE/SE/XC Series
Quarter-Turn Electric Actuator
Installation & Maintenance Manual
12/17/19
IOM8011 REVISION 01