Deye INGE 사용자 설명서 - 페이지 7

{카테고리_이름} Deye INGE에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Deye INGE 20 페이지. Hybrid inverter

Deye INGE 사용자 설명서
3.3.2 Battery temperature connection
1 2
Temp. CT
- 09 -

3.4 AC Input/Output Connection

・ Before connecting to AC input power source,please install a separate AC breaker
between inverter and AC input power source.This will ensure the inverter can be securely
disconnected during maintenance and fully protected from over current of AC input.The
recommended of AC breaker is 50A for 5kw and 80A for 8KW.
・ There are three terminal blocks with "Grid""Load"and "GEN"markings.Please
do not misconnect input and output connectors.
All wiring must be performed by a qualified personnel.It is very important
for system safety and efficient operation to use appropriate cable for AC
input connection. To reduce risk of injury,please use the proper
recommended cable as below.
Model
Wire Size
5/6KW
8AWG
7.6/8KW
6AWG
Chart 3-3 Recommended Size for AC wires
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection,be sure to open DC protector or
disconnector first.
2. Remove insulation sleeve 10mm length,unscrew the bolts,insert the AC input wires
according to polarities indicated on the terminal block and tighten the terminal screws.
Make sure the connection is complete.
(Region:US)
2
Cable(mm )
Torque value
8
1.2Nm
13
1.2Nm
(Region:EU)
- 10 -