Aqua PRO ECO550 설치 및 사용자 설명서 - 페이지 19
{카테고리_이름} Aqua PRO ECO550에 대한 설치 및 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Aqua PRO ECO550 20 페이지. Swimming pool heat pump
Aqua PRO ECO550에 대해서도 마찬가지입니다: 설치 및 사용자 설명서 (20 페이지)
Failure code
NO.
DISPLAY
1
E3
2
E5
3
E6
4
Eb
5
Ed
NO.
DISPLAY
1
E1
2
E2
3
E4
4
E7
5
E8
6
EA
7
P0
8
P1
9
P2
10
P3
11
P4
12
P5
13
P6
14
P7
15
P8
16
P9
17
PA
18
F1
19
F2
20
F3
21
F4
22
F5
23
F6
24
F7
25
F8
26
F9
27
Fb
28
FA
NOT FAILURE DESCRIPTION
No water protection
Power supply excesses operation range
Excessive temp difference between inlet and outlet water (Insufficient water
flow protection)
Ambient temperature too high or too low protection
Anti-freezing reminder
FAILURE DESCRIPTION
High pressure protection
Low pressure protection
Phases lack protection (three phase model only)
Water outlet temp too high or too low protection
High exhaust temp protection
Evaporator overheat protection (only at cooling mode)
Controller communication failure
Water inlet temp sensor failure
Water outlet temp sensor failure
Gas exhaust temp sensor failure
Heating (Evaporator) coil pipe temp sensor
Gas return temp sensor failure
Cooling (Titanium heat exchanger) coil pipe temp sensor
Ambient temp sensor failure
Cooling plate sensor failure
Current sensor failure
Restart memory failure
Compressor drive module failure
PFC module failure
Compressor start failure
Compressor running failure
Inverter board over current protection
Inverter board overheat protection
Current protection
Cooling plate overheat protection
Fan motor failure
Capacitor no charging protection
PFC module over current protection
16