ABB ACH580-31 빠른 설치 및 시작 매뉴얼 - 페이지 10

{카테고리_이름} ABB ACH580-31에 대한 빠른 설치 및 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ACH580-31 16 페이지. Converter modules with electrolytic dc capacitors in the dc link
ABB ACH580-31에 대해서도 마찬가지입니다: 매뉴얼 (16 페이지)

ABB ACH580-31 빠른 설치 및 시작 매뉴얼

13. Start-up the drive

WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If
you are not a qualified electrical professional, do not do electrical installation or maintenance work.
Use the control panel to do the start-up procedure. The two commands at the bottom of the display show the functions of
the two softkeys
and
depending on the context. Use the arrow keys
active view. Key
shows a context-sensitive help page.
?
1.
Power up the drive. Make sure that you
have the motor name plate data
available.
2.
Select the language you want to use
and press
(OK).
Note: After you select the language, it
takes a few minutes for the control
panel to wake up.
5.
In the Main menu, go to Parameters > Complete list > 95 HW configuration,
pressing
(Select) repeatedly to select parameter
7.
To complete the first start assistant,
select the values and settings when
prompted by the assistant. Continue
until the panel shows that the first
start is complete.
When the panel shows that the first
start is complete, the drive is ready for
use. Press
(Done) to enter the
Home view.
located below the display. The commands assigned to the softkeys are different
,
,
and
3.
In the First start assistant screen,
select Exit and press
95.01.
8.
The Home view shows the values of the
selected signals.
to move the cursor or change values depending on the
4.
In the Home screen, press
(Next).
(Menu) to enter the Main Menu.
6.
In parameter 95.01 Supply voltage,
press
Select supply voltage 380...415 V or
440...480 V and press
Go back to the Main menu by pressing
(Back) repeatedly.
In the Main menu, select First start
assistant and press
enter the First start assistant menu.
Continue with the following steps for
commissioning the ACQ580.
9.
Make additional adjustments, for
example, pump protections, starting
from the Main menu. Press
(Menu) in the Home view to enter the
Main menu.
Select Primary settings and press
(Select) (or
To get more information on the
Primary settings menu items, press
to open the help page.
10
(Edit).
(Save).
(Select) to
).
?