Control cable installation examples
This section shows examples for routing the control cables in frames R4 and R6...R9. Frames R1...R3 and R5 are similar to
frame R4.
R4
EIA-485 embedded fieldbus connection
You can connect the drive to a serial communication link with a fieldbus adapter module or the embedded fieldbus
interface. The embedded fieldbus interface supports the Modbus RTU protocol.
To configure Modbus RTU communication with the embedded fieldbus:
1.
Connect the fieldbus cable and the required I/O signals.
2.
If the drive is at the end of the fieldbus, set the termination switch to ON.
3.
Power up the drive and set the required parameters. Refer to
R6...R9
Fieldbus communication
.