NOTE:
Not typical for all size switches
Circuit Breaker Assembly Instructions
1.
Remove the (2) screws from the connecting link.
2.
Use a 5/16" wrench to remove the two 1/4-20 screws and
lock washers which secure the handle to the enclosure
flange. These screws are located on the underside of the
enclosure flange. Remove the old handle assembly from
the enclosure.
3.
Remove the mechanism from the panel and replace it
with the one provided. The mounting panel may need to be
removed to access the mounting screws.
4.
Hardware has been provided to mount a new disconnect
switch if necessary.
Siemens Industry, Inc. 3617 Parkway Ln, Peachtree Corners, GA 30092 www.usa.siemens.com
Disconnect Handle Replacement Diagram
E87010-A0137-T003-A4
5.
Install the new handle assembly onto the enclosure.
6.
Reinstall the two 1/4-20 screws and lock washers.
Make sure the handle housing is sealed against the
enclosure flange as this prevents the entry of moisture.
7.
Reinstall the connecting pin and retaining ring that connect
the handle link to the mechanism. The retaining ring should
not spin freely on the shaft after it is installed.
8.
No handle adjustment is required.
9.
Verify that the handle mechanism turns 'ON' and 'OFF' the
circuit breaker.
10. Verify that the door cannot be opened with the handle in
the 'ON' position.
4