Cisco Firepower 2130 매뉴얼 - 페이지 9
{카테고리_이름} Cisco Firepower 2130에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Cisco Firepower 2130 12 페이지. Rack-mount and ground the chassis
Cisco Firepower 2130에 대해서도 마찬가지입니다: 배포 매뉴얼 (8 페이지), 시작하기 (42 페이지), 설치 및 유지 관리 (26 페이지)
Rack-Mount and Ground the Chassis
c) Slide the release clip toward the rear on both inner rails, and then continue pushing the chassis into the rack until the
mounting brackets meet the front of the slide rail.
Figure 8: Inner Rail Release Clip
Inner rail release clip
1
Step 7
Use the captive screws on the front of the mounting brackets to fully secure the chassis to the rack.
What to do next
• See
• Install the cables according to your software configuration as described in the
Ground the Chassis
Note
Grounding the chassis is required, even if the rack is already grounded. A grounding pad with two threaded
M4 holes is provided on the chassis for attaching a grounding lug. The grounding lug must be Nationally
Recognized Testing Laboratory (NRTL)-listed. In addition, a copper conductor (wires) must be used and the
copper conductor must comply with National Electrical Code (NEC) code for ampacity.
You need the following items that you provide:
• Wire-striping tool
• Crimping tool
Ground the Chassis, on page 9
Getting Started
Guide.
Inner rail attached to chassis
2
for the procedure to ground the Firepower 2100.
Rack-Mount and Ground the Chassis
Ground the Chassis
Cisco Firepower 2100
9