TROUBLESHOOTING
Symptom
During installation, the ARISTA Mobile App
can't find the sensor when scanning for
devices in the area
Sensor is energizing the lights without motion
being detected in the space
Sensor doesn't detect motion when person
enters the space
Sensor's Red LED is on solid
Sensor is de-energizing the lights while
occupants are still in the space moving
Sensor leaves the lights energized long after
occupants have left the space
Verify power is supplied to the sensor
Verify the switch on the back of the sensor is in the 24 V position
Make sure the Blue LED is blinking slowly. If not, the sensor could already be provisioned into
another area. If this is incorrect, factory reset the device by pressing and holding the reset
button for more than 10 seconds
Make sure the phone/tablet and sensor are within 30 feet of each other
Verify zone configuration using the ARISTA Mobile App is correct
Verify sensor configuration (i.e. – wired vs. wireless)
Sensitivity may be set too high. Using the ARISTA Mobile App, lower the sensors sensitivity
setting
Change mounting location
Verify power is supplied to the sensor
Verify the switch on the back of the sensor is in the 24 V position
If Blue LED is blinking slow, the sensor hasn't been provisioned into the zone using the ARISTA
Mobile App and will not operate properly
Verify the sensor is detecting motion by walking underneath the sensor and verifying the
Green LED blinks briefly
Sensitivity setting may be set too low. Using the ARISTA Mobile App, increase the sensors
sensitivity setting
Verify sensor configuration (i.e. – wired vs. wireless).
Verify sensor configuration (i.e. – time delay)
Change mounting location
Replace Sensor
Change mounting location
Sensitivity setting may be set too low. Using the ARISTA Mobile App, increase the sensors
sensitivity setting
Verify sensor configuration (i.e. – time delay)