7001 Versa'larm
Tank Alarm
Operation, Maintenance
and Installation Manual
1. To install/replace the battery for the backup power feature, remove the two side screws and install 9 VDC battery (Duracell model MX 1604B2). After install-
ing battery, press the test button to activate the alarm to make sure the battery works properly. Reinstall side screws. See Figures 1 & 2 .
2. Determine mounting location for the VERSA'LARM. Make sure power outlet is within 6 feet of the VERSA'LARM. Make sure the outlet in on a separate
circuit breaker from any other device and not on a switched receptacle to maintain power integrity. Mount the VERSA'LARM using two #8 x 1 1/4" self tapping
screws(not included). Use #8 plastic anchor if mounting to sheet rock. See Figure 2
3. If Auxiliary Contacts are used continue, else go to step 4. Remove cover from base and remove 1/2" electrical knockout from base. Use 16 - 2 AWG stranded
wire - make sure there is at least 6" of wire inside of enclosure. Install a 1/2" strain relief with jam nut. Connect wires for required application using wire nuts.
Caution! - When installing wires, route all wires away from sharp objects & internal components. See figures 3A & 3B.
4. Use the included label identification kit or permanent marker/user supplied label to identify the alarm condition. Use the tick marks for alignment. See Figure 2.
5. Connect a UL listed switch (rated 9 VDC, 200 ma MINIMUM) such as a float switch, pressure switch, etc. to the two position terminal block on the
VERSA'LARM. One wire per terminal. The alarm is activated by a closed switch. See Figure 2. Caution! - When installing the "signaling switch" refer to it's
installation instructions for proper installation.
6. Plug in the power supply into a 120VAC, 50/60 HZ standard wall outlet. For UL applications, remove center screw on receptacle and place cord from wall
mount transformer inside the plastic cord holder. Secure plastic cord holder to the receptacle by reinstalling screw to the center hole of receptacle. See Figure 2.
For Canadian applications DO NOT INSTALL Plastic Cord Holder! The green "Normal" light should come on.
7. Test the system by pressing the "Test" switch or by activating the "signaling device". The buzzer and the red warning light will be "on". The green "Normal"
light will be "off". Press the "Silence" switch. The buzzer will silence but the alarm light will remain "on". Deactivate the "signalling device." The alarm light will
turn "off" and the green "Normal" light will turn "on" indicating the system is now in a normal condition. Since the VERSA'LARM is equipped with "Auto
Reset", reactivating the "signaling device" for a new test cycle will reactivate the buzzer and alarm light.
8. Test product weekly to ensure system integrity.
Figure 1 - Installing/Replacing Battery
Battery Strap Connector
Battery Holder
Place Duracell model MX1604B2
9 VDC Battery into battery holder
for battery back up.
Figure 3A - Installing Field Wiring for
Auxillary Contacts
1/2" Electrical
knockout
SJOW Cord
16-2 AWG
Jam Nut
1/2" Strain
Release
Base
Alarm Systems
Control Panels
PO Box 827
Hawley, MN 56549
TM
9 V Battery
Wire Nuts
Float Switches
(218) 483-3034
Figure 2 - Mounting
Use #8 X 1 1/4"
Self Tapping screws
Cover
Application
Identification
Terminal Block for Signaling Device
must be UL Listed Switch rated
9VDC, 200 ma MINIMUM!
I.E.Float Switch
Figure 3B - Wiring Diagram for Optional Auxillary
Auxillary Con
tacts
White - Common
Red - Normally Closed
Black - Normally Ope
Class 2, 24 VDC/VAC( 50/60HZ)
500 Milliamps MAXI
MUM!
Alderon Industries, LLC
P.O. Box 827
Hawley, MN 56549
Page 2 of 2
Leak Detection Systems
Fax (218) 483-3034
Mounting Hole (2)
Side Screw
Enviromental Protection System
TM
VERSA'LARM
Patent # 6,683,535
Normal
Alarm
120VAC Wall mount
Base
Test
Silence
AUTO RESET
receptacle
AC
Adaptor
Versa'larm
Enviromental Protection System
TM
Model: VA0
VERSA'LARM
Applica-
Patent # 6,683,535
Normal
Alarm
tion for
Silence
Test
AUTO RESET
Remote
C
NO
Application for
Equipment Shutoff
C
V-UL Listed Class 2
transformer 500
MA MAX
NC
L - Load
P/N 10026 Rev B
10/28/02
Phone: 218.483.3034
Fax: 218.483.3036