aldes ZRT-R Series 사용 설명서 - 페이지 7
{카테고리_이름} aldes ZRT-R Series에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. aldes ZRT-R Series 8 페이지. Zone register terminal
3. INSTALLATION
Regulator must be installed in a metallic air duct as pictured above. D represents the regulators
maximum outer diameter.
Rigid Duct
or Register
Box
The CAR3 should be installed in accordance with all applicable building and mechanical codes. If
installed in a metal duct or duct collar with a flexible duct connector (listed to UL 2043), the CAR3 must
be inserted at least 1.2 times the duct diameter from the flexible duct and/or duct connector.
Duct Collar
Flex Duct
L ≥ 1.2 D
L ≥ 1.2 D
D
Orient the CAR3 according to the airflow direction
indicated on the device. Horizontal or vertical mounting
is acceptable.
360°
3
Flex Duct
D
CAR3
Duct Collar
Duct Collar
or Grille