Advanced Energy Thyro-PX Anybus Manual - Page 6

Browse online or download pdf Manual for Control Unit Advanced Energy Thyro-PX Anybus. Advanced Energy Thyro-PX Anybus 13 pages. Ethernet ip module

®
Advanced Energy
Table 5. Configuration (Continued)
Name
Motorpotentiometer =
Master
Setpoint Error
Local remote
configuration
Configuring Flexible Link Parameters
The flexible link parameters have been designed to allow access to Thyro-PX internal data, such as
parameters and actual values.
There are up to 20 flexible link parameters for writing data and up to 20 flexible link parameters for
reading data.
Most flexible link parameters have a preconfigured, default definition, which can be modified using
the Thyro-Tool Pro PC software. All device parameters and actual values are selectable from the
drop-down list.
For special applications, the flexible link parameters can be manually configured via Ethernet IP
using the configuration assembly (see

Default Flexible Links

Table 6. Default flexible links
Flexible Link
Flexible read-link 01 r
Flexible read-link 02 r
Flexible read-link 03 r
57010163-00A
Status/Selection
Motorpotentiometer =
Master
Zero
Last valid master
setpoint
Last valid error setpoint
Unchanged behavior
Automatic switch to local The unit will automatically switch to local mode when
Ignore master in local
"Write and Read Assemblies"
Type
FLOAT
Power Controller #1: Total power - read
FLOAT
Power Controller #1: L1 Urms - read
FLOAT
Power Controller #1: L1 Irms - read
Thyro-PX
Description
thereby avoiding unwanted effects due to an
incomplete change.
When enabled, the value of the motorpotentiometer
continuously follows the master setpoint while in
remote operation, so that no setpoint leap occurs
during the switch-over to the local setpoint.
Zero is used as the setpoint when the master setpoint is
missing.
The last valid master setpoint is used as the setpoint
when the master setpoint is missing.
The last valid error setpoint is used as the setpoint
when the master setpoint is missing.
Configuration of the master's influence to the local
remote behavior.
the communication with master is interrupted.
When the unit is in local mode, data and commands
from the master will be ignored.
on page 8).
Default Link Setting
®
Anybus
Ethernet IP
®
Thyro-PX
Anybus
Ethernet IP
6