AirTest TR9230 User Manual - Page 2
Browse online or download pdf User Manual for Controller AirTest TR9230. AirTest TR9230 2 pages. Vav zone control for temperature and co2
shall begin to control to temperature of ___ºF intended for setback or unoccupied
mode.
6. When in setback mode the controller will revert to control temperatures at the
occupied mod set point if any of the of the following conditions exist: 1) if either
of the temperature adjustment buttons on the wall mount sensor/controller are
pressed the sensor will operate in occupied mode for 2 hours (setback reset), or
2) if CO
levels rise to levels greater than 50 ppm above outside levels or 3) the
2
controller shall also be able to receive a closed contact signal to allow control of
setback based on an external timer. A closed contact signal will indicate the
system should be in occupied mode.
Control Of Outside Air At the Central System
1. When outside conditions are such that outside air can be used for free
cooling, CO
2
economizer based cooling.
2. The central outdoor intake will be designed to provide a minimum level of
ventilation during all occupied hours. This minimum setting on the air intake
should be ____% of the design ventilation rate for all zones served.
3. Each zone sensor/controller shall provide a CO
back to a central system or used as a control signal for the outside air intake.
Regulation of outside air to the space shall be based on the single highest
CO
level received from all of the zones served.
2
4. The controller shall also be capable of providing a linear 0-10V analog
temperature signal for reporting or monitoring purposes by a central system.