4. AUX Power Wiring
The control panel can provide a maximum of 700mA of current for modules, powered detectors, relays, LED's etc.... If the total current
required exceeds 700mA an additional power supply is required (e.g.,PC5200, PC5204). See list below.
NOTE: Min/max operating voltages for devices, sensors and modules is 9.5V
Refer to the list of Compatible Devices on the first page for the current draw of individual devices
5. PGM Wiring
PGMs switch to ground when activated by control panel.
Connect the positive side of the device to be activated to the AUX+
Terminal. Connect the negative terminal to the PGM.
current output is as follows
•
PGM 1, 3, 4 .................... 50mA
•
PGM 2 .......................... 300mA
For currents levels greater than 300mA a relay is required.
PGM2 can also be used for 2-wire smoke detectors.
NOTE: Use SEOL resistors on Fire Zones ONLY.
2-wire Smoke Detectors Initiating Circuit
•
Style B (Class B), Supervised, Power Limited
•
Compatibility Identifier ........................................................ PC18-1
•
DC Output Voltage..................................................... 9.8-13.8 VDC
•
Detector Load ............................................................. 2 mA (MAX)
•
Single-end-of-line (SEOL) Resistor ..................................... 2200Ω
•
Loop Resistance............................................................24Ω (MAX)
Standby Impedance.................................................. 1020Ω (ΝΟΜ)
•
•
Alarm Impedance ........................................................570Ω (MAX)
•
Alarm Current ............................................................ 89 mA (MAX)
Compatibility ID For FSA-210B Series is: FS200
6. Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an
RJ-31x Connector as indicated.
For connection of multiple devices to the telephone line, wire in the
sequence indicated.
Telephone format is programmed in section [350].
Telephone Call Directions are programmed in section [351]-[376].
7. Ground
Ground Installation
Tighten nut to break paint and make
good connection to the cabinet
Hardware Installation (Cont.)
8. Battery
A sealed, rechargeable, lead
acid battery or gel type battery is
required to meet UL require-
ments for power standby times.
NOTE: UL Residential/Commer-
cial Burglary installations require
4Hrs Power Standby time.
NOTE: UL/ULC Residential Fire
& Home Care installations
require 24 Hr power standby.
ULC Commercial Burglary
and Fire monitoring installations
require 24 Hr power standby.
PGM 1, LED Output with current limiting resistor and Optional Relay
driver output
4-wire Smoke Detectors
RM-1/RM-2 POWER LOOP
SUPERVISORY RELAY
T-1
R-1
TIP
RING
Standby Battery Guide
Battery Charging Current: 400 mA
Batt
Standby
Size
4Hr
24Hr
-------------------------------------------------
4Ahr
700mA
----
7Ahr
700mA
180mA
14Ahr
700mA
470mA
NOTE:
Replace batteries every 3-5 years.
Battery capacity will deteriorate with
age and number of charge/discharge
cycles
- 14V
DC
DC
RJ-31X
9. AC Wiring
AC Wiring
UL Listed Installations
Primary: 120VAC/60Hz./0.33A
Secondary: 16.5VAC/40VA
DSCPTD 1640 Plug-in, Class 2
Transformer.
NOTE: Do not connect trans-
former to a receptacle controlled
by a switch. (UL Listed Installations
Only)