again. The parameter flow chart is shown in Fig. 3
Table 4. Temperature and Alarm Parameter
Symbol
Note 11. The SV can also be set directly during the normal operation mode. Press (^) or (v) key to switch
the display from process value (PV) to set value (SV). Press (^) or (v) key again to increase or decrease SV
by 1 degree.
i.

Relay J1 value

① When AH1=AL1,relay is disabled,
② AH1>AL1 is for absolute high alarm. See fig. 4.
③ AH1<AL1 is for absolute low alarm. See fig. 5.

5. Auto-Tuning

Auto-Tuning function (also called self tuning) can automatically optimize the PID parameters for the
system. The auto-tuning function will heat up the system then let it cool down. It will repeat several
times. Based on the response time of the system, the built-in artificial intelligence program will
calculate and set the PID parameters for the controller.
A)To activate auto-tuning, press and hold
auto-tuning is in progress. When "AT" stops blinking, the auto-tuning is finished. Now, newly calculated
PID parameters are set and are used for the system. Please note that Auto-tuning is only for PID control
mode (when "outy"is set at 1 or 2)
Description
SV
Target temperature (Set
Value)
AH1
Alarm on temperature
AL1
Alarm off temperature
End
Exit
Figure 6
key until the "AT" indicator starts to blink, which indicates