Auber Instruments SKX-400 Instruction Manual - Page 2

Browse online or download pdf Instruction Manual for Measuring Instruments Auber Instruments SKX-400. Auber Instruments SKX-400 3 pages. Four-channel temperature meter

AUBER INSTRUMENTS
4. Parameter Setting
Table 1. Parameter list
Code
Name
Description
System parameters (first layer of menu)
Parameter
LOCK=18, Set data unlock
LocK
lock
LOCK≠18, Set data lock.
Thermocouple: K; E; J; T; S
TS
Input type
RTD: Cu50; Pt2 (pt100)
This parameter is disabled in this
ALP
Alarm type
model.
Kt
Cycle time
Output cycle time
Decimal point
Set the position of the decimal point
Dp
position
for the measured value.
Display high
P-SH
limit
Input display range.
Display low
P-SL
limit
C: Celsius F: Fahrenheit
If the parameter is changed, the
CF
Display unit
controller needs to run Auto-tuning
again.
Parameters for each channel (second layer of menu)
"n" is the channel number. For example, SP1 is the set value for channel 1
Set Value for
Set the temperature set value (SV)
SP(n)
channel 1 ~ 4
for each channel
Pb is used to set an input offset to
PB(n)
Input offset
compensate the error produced by
the sensor or input signal itself.
Set when PI or PID control is
performance.
Proportional
When P = 0, the controller is
kP(n)
Constant
under ON/OFF mode.
This parameter will in use when it
is not zero.
Eliminates offset occurring in
kI(n)
Integral time
proportional control.
Prevents overshoot and/or
kD(n)
Derivative time
undershoot caused by integral
action effect.
The Hysteresis Band parameter Hy
is also referred as Dead Band, or
Hysteresis
Differential. This permits protection
band (for
of the on/off control from high
Hy(n)
ON/OFF
switching frequency caused by
mode)
process input fluctuation. Hysteresis
Band parameter is used for on/off
control.
1: Auto-tune is ON
AT(n)
Auto tuning
0: Auto-tune is OFF
0: Heating mode
COL(n)
Control mode
1: Cooling mode
2021.11
Setting
Initial
range
Setting
0 ~ 50
18
-
K
-
0
-
10
0-1
1
1300
0
C, F
C
4.1 Change system parameters (first layer of menu)
Hold SET key for about 3 seconds and you will enter the first level menu.
Channel 1 display will show the parameter name and channel 2 display will
P-SL ~
100
show the parameter value. Press ◄(shift key), ▲ and ▼ keys to change the
P-SH
parameter value. Press SET key to save the change and change to the next
parameter.
± 20.0
0.0
4.2 Change parameters for each channel (second layer of menu)
Hold CH1/CH2/CH3/CH4 key for about 3s to enter the parameters for that
1 ~
100
channel. Similarly, press ◄(shift key), ▲ and ▼ keys to change the
100
parameter value. Press SET key to save the change and change to the next
parameter.
0 ~
500
3000
5. Alarm & output modes
This thermometer has four separate dry relay outputs. They can be used as
0 ~
100S
fully functional PID outputs (relay outputs), or they can be used as absolute
2000S
high/low alarm or ON/OFF control mode.
For absolute high temperature alarm, please set kP(n) to 0 and COL(n) as 1.
So when PV(n) is over SP(n) + Hy(n), output will be enabled. When PV(n) is
0.1 ~
1.0
below SP(n) – Hy(n), output will be disabled.
50.0
For absolute low temperature alarm, please set kP(n) to 0 and COL(n) as 0. So
when PV(n) is below SP(n) - Hy(n), output will be enabled. When PV(n) is over
SP(n) + Hy(n), output will be disabled.
0 ~ 1
0
0 ~ 1
0
ON/OFF mode will be very similar to the alarm above. Please set kP(n) to 0
and set COL(n) to 0 as heating mode and 1 as cooling mode. Then, set the Hy
to the desired range based on control precision requirements. Smaller Hy
values result in tighter temperature control, but also cause the on/off action to
occur more frequently.
Figure 5. Output example. kP(n) = 0, COL(n) = 0. Low temperature alarm or
heating mode. Relay off when PV ≥ SP + SV; relay on when PV ≤ SP – SV.
WWW.AUBERINS.COM
Figure 4. Operation flow chart
PV
103
SP+Hy
100
SP
SP-Hy
97
Relay On
P2/3