Menu Level (1.4)
Fault Status
This menu shows the status of the two signalling channels used by the loop interface and the
communicating device. If more than one interface is used, please refer to Appendix B, page 11.
Alarm Status
Battery Level
The received signal strength at the loop interface from the device is shown as L1
Signal Level
by a percentage indicating the signal strength. Similarly the received signal at the device is shown
as L1
Manual Update
Ident
If you have moved or re-installed a device, complete a manual update before checking the signal
level.
The L1
when requested manually by selecting the 'Manual Update' option described below.
Menu Level (1.5)
Fault Status
When selected the status of all devices is updated. The current status can then be viewed as
described in the 'Signal Level' Menu.
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
Menu Level (1.6)
Fault Status
This menu shows the unique five digit identification number for the device. This may be recorded
on site drawings or the radio survey document for maintenance purposes.
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
Menu Level (1.7)
Fault Status
This menu indicates the detector type on a Combined Sounder Visual Indicator Base.
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
Type
D followed by the signal strength.
D level is updated every 300 seconds. The L1
Ch 1 LI
D = Device to Interface signal on channel 1
Ch 2 LI
D = Device to Interface signal on channel 2
Ch 1 LI
D = Interface to Device signal on channel 1
Ch 2 LI
D = Interface to Device signal on channel 2
D level is updated every 12 hours or
60 - 100 = Good signal level
50 - 59 = Medium Signal level*
40 - 49 = Low Signal level
30 - 39 = Caution Signal level
10 - 29 = Fault Signal Level
0
LI
D XXX
PP2286/2019/Issue 13
Page 8 of 12
D followed
= No Signal level