Troubleshooting Guide

⚠ WARNING
Read all safety information found in this manual and in the Material Safety Data Sheets
(MSDS) for any refrigerants used with this machine prior to performing any service on this machine.
SYMPTOM: Machine will not start, no sound when power switch turned 'On'
CAUSE
Power cord not plugged in, or no power in outlet
Machine in High Pressure Shutoff
Motor in Thermal Overload
SYMPTOM: Machine tries to start, makes humming/buzzing sound
CAUSE
Low voltage at source outlet
Voltage drop in extension cord
Too much back pressure on compressor
SYMPTOM: Machine pumps into high pressure shutoff
CAUSE
Valve on machine or recovery cylinder not fully
opened
Restriction in output hose
SYMPTOM: Pumps liquid slowly
CAUSE
Flow restrictions on input side of machine
Trapped liquid in system
SOLUTION
Check power cord, try different outlet
See symptom below
Allow motor to cool down
SOLUTION
Try different power source outlet
See Extension Cord sizing guidelines on Page 4
Try starting the machine with the valves on
the Manifold Gauge Set closed to reduce back
pressure on compressor
SOLUTION
Check that the valve on the recovery cylinder is
fully opened
Check hoses for any blockage;
Remove any core depressors
SOLUTION
Use 3/8" hoses;
Remove "Schrader" valve cores and core
depressors
Cycle system compressor for a few seconds to
move trapped liquid to another area;
Check for condensation on system, and apply
heat as needed;
Check for condensation at hose fittings, and
apply heat as needed
15
© 2012 APPION INC. - ALL RIGHTS RESERVED
G1SINGLE OPERATION MANUAL