DRAINAGE HOLE (P13)
This air conditioner has a double system to drain the condensated moisture automatically. Before
installing the Air Conditioner choose which is the suitable system for your installation. Please read
carefully the follow instructions.
System "A": drill a hole through the wall measuring 30 mm in diameter in the position shown in
the paper template. Drainage occurs by gravity. For this reason, it is essential for the drain line to
have a minimum downward inclination at least 3 degrees throughout its length: connect the
drain pipe (from rubber terminal) to the air conditioner (back side) after unplugged the black rub-
ber cup (see picture P13). With this solution you can drain the condensated moisture to a suitable
place.
System "B": in case of impossibility to install drainage pipe as showed on "A" system, do not
unplug the black rubber cup (picture P13). The condensated moisture will go outside by the two
big pipes (see picture P14). If you choose this solution be sure that the condensate moisture doesn't
cause any problems to your neighbours.
2.4 FASTENING THE BRACKET (P6)
-Drill the holes for anchoring the fastening bracket to the wall using preferably the 6 holes shown
in black on the paper template. If the wall is not sturdy enough it is advisable to use extra anchor
bolts using the holes showed in grey on the paper template.
-The anchor bolts provided require a 8mm holes; the wall should be inspected to determine if pro-
vided bolts are useful or if it is necessary to use a different anchorage. The manufacturer is not
liable in case of underestimation of the structural consistency of the anchorage made at the time
of installation.
2.5 INSTALLATION OF THE PIPES
-After drilling the holes, the plastic pipes supplied with the air conditioner need to be fitted
through them.
-The pipe with a diameter of 160mm (fresh air intake) has to be fitted in the right hole. The
length of the pipes should be equal to the depth of the wall plus 10 mm. Use a normal hacksaw
to cut the supplied pipes to the correct length. Remember that the modification must to have the
same inclination of the holes (minimum 3 degrees).
-The tube diameter is nearly the same as that carried out using the 162 mm nominal diameter
core drill therefore you may need to slightly force the introduction of the pipe using, in difficult
cases, a normal rubber hammer and a small piece of timber to gently tap the tube into the hole.
-Please use the same instructions to fit the left hand tube (AIR discharge pipe) using the supplied
pipe with a diameter of 150mm. The tube diameter is slightly smaller than that carried out using
the 162 mm nominal diameter core drill.
-Please centre the pipes into the holes in the wall and insulate and seal their perimeters to pre-
vent air and humidity infiltration using polyurethane foam and using plaster as finishing on the
inside wall.
2.6 FITTING THE GRATINGS (P7,P8,P9,P10)
To fit the external two gratings please proceed as follows: familiarise yourself with the fitting of
the grating to the tube, before installation. Insert the cords through the centre of the grating. One
grating fits on the outside of the tube and the other fits inside. The air intake is the bigger hole
and the grating therefore fits on the outside of the air intake tube. Insert the supplied cord into
the hole. Fold the outer grating in half grasping the cord with your free hand. Insert your arm
inside the pipe with the grating and push all the way to the outside. Let the grating unfold and
pull the cord toward you. One grating fits on the outside of the tube and the other fits inside.
With a little patience and manipulation the 2 gratings will fit the end of the tubes. Grasping the
cord, insert your fingers between the fins and pull the grating toward you until the same is proper-
ly slipped in the pipe, keeping the fins in vertical position. If the external grating is accessible to
prevent its removal, it is recommended to fasten it to the wall with wall plugs and screws with a
diameter of 6 mm. Tighten the cord and fasten it to the dent on the internal flanges.