Automated Logic MX16160 Technical Instructions - Page 7
Browse online or download pdf Technical Instructions for Extender Automated Logic MX16160. Automated Logic MX16160 7 pages.
Table 4. Input Channel Numbers
Channel
Point
Signal Type
Number
Thermistor
38
UI 8
mA or Volts
38
Digital
28
Thermistor
39
UI 9
mA or Volts
39
Digital
29
Thermistor
3A
UI 10
mA or Volts
3A
Digital
2A
Thermistor
3B
UI 11
mA or Volts
3B
Digital
2B
Thermistor
3C
UI 12
mA or Volts
3C
Digital
2C
Thermistor
3D
UI 13
mA or Volts
3D
Digital
2D
Thermistor
3E
UI 14
mA or Volts
3E
Digital
2E
Thermistor
3F
UI 15
mA or Volts
3F
Digital
2F
Thermistor
30
UI 16
mA or Volts
30
Digital
20
† Celsius values can only be displayed in SuperVision when the Function
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to
the Eikon User's Guide for more information.
§ Use the Point Configuration or Point Help feature available in SuperVision
v2.0 or later.
Revised 9/13/00 • MX16160
†Range
Offset
Gain
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
-17° to 213° F
0.00
15.88
-27° to 100.6° C
0.00
15.69
0 to 20mA
§
§
0 to 5V
Troubleshooting
LEDs
The MX16160 module has several LED
indicators to show the status of certain
functions.
Power - lights when power is being supplied
to the module.
Run - flashes to indicate a normal condition.
Expander Comm - flashes to indicate
expansion bus communications are valid.
Digital Output Status - lights when the digital
output is activated.
Protection
The MX16160 module is protected by internal
solid state Polyswitches on the incoming
power. These Polyswitches are not
replaceable and will reset themselves if the
condition that caused the fault returns to
normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in SuperVision. Refer to
the SuperVision User's Guide for more
information about the module status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
of manufacture. (The month digit is in
hexadecimal.)
7
© 2000 Automated Logic Corporation