Automationdirect.com Productivity 1000 P1-08NA Manual

Browse online or download pdf Manual for I/O Systems Automationdirect.com Productivity 1000 P1-08NA. Automationdirect.com Productivity 1000 P1-08NA 4 pages. Ac input

Automationdirect.com Productivity 1000 P1-08NA Manual
Input Specifications
Inputs per Module
Rated Voltage
Operating Voltage Range
AC Frequency
Input Current
Maximum Input Current @ Temp
Input Impedance
ON Voltage Level
OFF Voltage Level
Minimum ON Current
Maximum OFF Current
OFF to ON Response
ON to OFF Response
Status Indicators
Commons per module*
*C1 and C2 must be jumped together by an external wire during 240VAC applications.
Sales 800-633-0405
8
100–240 VAC
80–288 VAC
47–63 Hz
7mA @ 100VAC (50Hz)
8.5 mA @ 100VAC (60Hz)
14.2 mA @ 240VAC (50Hz)
17mA @ 240VAC (60Hz)
26mA @ 60°C (288VAC)
15k: (50Hz), 12k: (60Hz)
> 70VAC
< 20VAC
5mA
2mA
< 10ms
< 25ms
Logic Side (8 points)
2 Isolated (4 points/common) @ 120VAC
2 Non-Isolated @ 240VAC
P1-08NA AC Input
P1-08NA
The P1-08NA AC Input Module provides
eight 100–240 VAC inputs for use with the
Productivity1000 system.
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
C1
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Schematic & Wiring Diagram . . . . . . . . . . . . . . . . . . . . 3
1
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 4
2
Terminal Block Specifications . . . . . . . . . . . . . . . . . . . . 4
3
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4
C2
5
6
7
8
100-240VAC
INPUT
Terminal Block sold separately, (see wiring options on page 3).
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement (See www.productivity1000.com for details).
www.productivity1000.com
1000
1