Automationdirect.com AcuAMP ACTS050 Series Installation Instructions

Browse online or download pdf Installation Instructions for Transducer Automationdirect.com AcuAMP ACTS050 Series. Automationdirect.com AcuAMP ACTS050 Series 2 pages.

Specifications
Power Required
24 VAC/DC (+/-10%)
Power Consumption
< 2VA
Outputs
Solid state switch, N.O. and analog output
Switch Rating
1A @ 240VAC maximum
Offstate Leakage
< 10μA
0.50 sec. 5% over set point
Switch Response Time
0.20 sec. 50% over set point
0.15 sec. 100% over set point
Switch Hystersis
5% of setpoint
1-50 Amps (ACTS050)
Switch Setpoint Range
4-200 Amps (ACTS200)
Single turn potentiometer
Switch Setpoint Adjust
Setpoint displayed on sensor
1.1x range continuous
Sensed Current
3x range for 6 seconds
Limit
5x range for 1 second
Analog Output Signal
4-20mA
Analog Output
500Ω max
Impedance
< 0.30 sec. 90% step change
Analog Output Response
< 0.40 sec. 100% step change
Accuracy
+/-1%
Isolation Voltage
UL508, UL tested to 1480VAC
Frequency Range
40-400 Hz, Average Responding
Sensing Aperture
0.75 in (19mm) dia.
-Temp -4 to 122°F (-20 to 50°C)
-Humidity 0-95% RH, Non-condensing
Environmental
-Pollution degree 2
-Altitude 2000 meters
Case
UL 94V-0 Flammability rated thermoplastic
cULus listed E222847
Certifications
CE
For products intended for the EU market, the
following is applicable to the CE compliance of
the product:
The ACTS050/ACTS200 Series may comply with EN 61010-1
CAT III 300V max line-toneutral measurement category. If
insulated cable is used for the primary circuit, the voltage rating
of the measurement category can be improved according to
the characteristics given by the cable manufacturer.
Use 24V input power and fuse at 5 amps. Power source
overvoltage category I as defined per EN 61010-1.
Part Number Key
ACTS 050 - 42 - AA - 24 - FD
CASE STYLE
FD - Fixed Core with setpoint display
POWER SUPPLY
24 - 24 VAC / DC
OUTPUT
AA - Normally Open
solid state switch
ANALOG OUTPUT
42 - 4 to 20 mA
RANGE
050 - 0-50 Amps AC (setpoint 1-50A)
200 - 0-200 Amps AC (setpoint 4-200A)
SENSOR TYPE
ACTS - AC current transducer and switch
Warning! Risk of hazardous voltage
When operating the device, certain parts may
carry hazardous live voltage (e.g., primary
conductor, secondary terminals). The device
should not be put into service if the installation is
not complete.
Warning! Risk of electric shock or
personal injury
Safe operation can only be guaranteed if the
device is used for the purpose for which it was
designed and within the limits of the technical
specifications. When this symbol is used, it
means you should consult all documentation to
understand the nature of potential hazards and
the action required to avoid them.
AutomationDirect.com (ADC)
3505 Hutchinson Road, Cumming, GA 30040
Phone: (800) 633-0405 or (770) 889-2858
ACTS - Inst - Rev 1
0820
P-N 893020015
ACTS050/ACTS200
SERIES
INSTALLATION
INSTRUCTIONS
Part No. ACTS050-42AA-24-FD
Quick Start Guide
1. Mount the sensor on a surface, if needed.
2.
Run the wire to be monitored through the
aperture.
3. Connect output wiring.
a. Use 30-12AWG copper wire rated 75˚C min
and tighten terminals to 7 in-lbs.
b. Ensure the power supply voltage matches the
model you are installing.
c. Energize the power to the sensor.
4.
Adjust setpoint.
a. LED will display the RMS value of AC current,
which will cause the output to change state.
b. Turn the potentiometer until your target
current value is displayed.
5. Analog signal output.
a. The analog output is powered from the sensor
power source.
b. The signal is proportional to the sensor range
selected.
®