Autopilot APCECOD Manual - Page 9

Browse online or download pdf Manual for Controller Autopilot APCECOD. Autopilot APCECOD 17 pages. Deluxe digital co2 controller

Page 8
APCECOD
"HOW TO calibrate" CO2 PPM
1) Place the controller outdoors in a shaded area. Do not place in
direct sunlight. Keep away from people, animals and other CO2
emitting areas.
Note: If calibration will be in a high traffic (vehicles)
area or a highly populated area a slightly increased
calibration to around 400-475 PPM is recommended.
3) Plug in the controller and allow to "warm up" for a minimum of
30 minutes. For best results, allow to "warm up" for an hour or
longer.
4) Press Calibrate CO2 PPM to activate the automatic calibration.
The new CO2 level
(C
380_PP) will be displayed. Press the up or
down button to change the calibration setting. DO NOT exhale or
breathe on the unit while activating the calibration function.
5) Press Enter / Reset to start the calibration sequence,
(Co2_CAL) will be displayed and CO2 calibration LED will be
blinking. Leave controller alone for about 10 minutes.
6) When calibration is complete the display window will return to
normal display and functions. Place the sensor back into the
grow area. All other functions remain as they were prior to
calibration.