Fault modes
6.3
Error/fault
Unohab does not
start or
impeller does not turn
(no longer turns)
Vibrations
Abnormal noises
Unohab no longer
performs at
maximum ventilation
speed
6.4
End of life and disposal
WARNING
When dismantling, live parts can be exposed, which can result in electric shock if touched. Before
dismantling, isolate the unit from the mains power supply and protect against being switching on again!
Parts and components of the fan, whose service life has expired, e.g. due to wear and tear, corrosion, mechanical
load and/or other effects that cannot be directly discerned, must be disposed of expertly and properly after
disassembly in accordance with the national and international laws and regulations. The same also applies to
auxiliary materials in use. Such as oils and greases or other substances. The intended and unintended further use
of worn parts, e.g. impellers, rolling bearings, filters, etc. can be a hazard to people, environment as well as
machines and systems.
Unohab Cavity Wall Installation Kit
Causes
– Mains power supply failure 230 V
– Control voltage failure 12 V DC
– Operating mode Supply air active
– Plug not connected to Unohab
or cable break
– Ventilation stage 0 activated
– Impeller blocked
– Motor defective
– Controller defective
– Contamination of impellers
– Bearing damage
– Grinding impeller
– Bearing damage
– Mechanical damage
– Coarse 50% - Filter and/or
protection guard contaminated
– Design-inner panel is closed
– Ventilation stage not selected
– Bearing damage
– Heat accumulator contaminated
12
Installation and Operating Instructions
Troubleshooting
Check mains power supply
Check connections according to wiring diagram
Replace switching power supply Unohab PSF / PSD
Change operating mode
(target function no fault)
Check plug and control for cable breaks if
necessary
Change operating stage
Note external contact
Clear blockage, clean, if necessary Contact
Airflow customer services
Contact Airflow customer services
Check connections according to wiring diagram
Contact Airflow customer services
Clean
Replace fan
Contact Airflow customer services
Clean impeller, replace fan if necessary
Contact Airflow customer services
Replace fan
Contact Airflow customer services
Replace defective components
Contact Airflow customer services
Check Coarse 50% -filter and protection guard
for contami-nation and replace Coarse 50% -
filter or clean protection guard
Open design–inner panel
Increase ventilation stage
Replace fan
Contact Airflow customer services
Clean (see page 11)