Dell PowerEdge 2950 Instructions Manual - Page 6
Browse online or download pdf Instructions Manual for Server Dell PowerEdge 2950. Dell PowerEdge 2950 15 pages. Cabling instructions for the -48 vdc power supply
Also for Dell PowerEdge 2950: Information Update (50 pages), Installation Information (11 pages), Installation Manual (10 pages), Update (2 pages)
CAUTION:
Never defeat the ground conductor or operate the equipment in the absence of a suitably installed
ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain
that suitable grounding is available.
Input Requirements
Supply voltage:
Current consumption:
Kit Contents
•
Tyco 556879-3 connector housing (1) or equivalent
•
Tyco 556880-2 connector contacts (3) or equivalent
•
AMP 2-320568-2 ring-tongue terminal (1) or equivalent
•
#8-32 nut equipped with lock washer (1)
Required Tools
•
Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated
copper wire
NOTE:
Use alpha wire part #3080 or equivalent (65/30 stranding)
•
One UL 1015 10 AWG, 2 m maximum (stranded) black wire (–48 VDC)
•
One UL 1015 10 AWG, 2 m maximum (stranded) red wire (48 VDC return)
•
One UL 1015 10 AWG, 2 m maximum green, stranded wire (optional connector ground)
•
One UL 1015 10 AWG, 2 m maximum green/yellow, green with a yellow stripe, stranded wire
(safety ground)
•
AMP 90871-1 hand-crimping tool or equivalent
4
Cabling Instructions for the –48 VDC Power Supply
–
(48–60) VDC
20 A maximum