Dell PowerEdge M915 Getting Started Manual - Page 10

Browse online or download pdf Getting Started Manual for Switch Dell PowerEdge M915. Dell PowerEdge M915 14 pages. Dell poweredge blade servers getting started guide
Also for Dell PowerEdge M915: Release Notes (27 pages), Manual (25 pages), User Manual (23 pages), Important Information Manual (35 pages), Getting Started Manual (12 pages), Getting Started Manual (12 pages), Owner's Manual (3 pages), Portfolio Manual (27 pages), Getting Started Manual (12 pages)

Dell PowerEdge M915 Getting Started Manual
Power — Enclosure
Heat dissipation
NOTE: Heat dissipation is calculated using the
power supply wattage rating.
Maximum inrush current
System Voltage Requirements
NOTE: This system is also designed to be connected to
IT power systems with a phase to phase voltage not
exceeding 230 V.
DC/DC power supply (per power supply module)
Wattage
Connector
Heat dissipation
Maximum inrush current
System Voltage Requirements
NOTE: Heat dissipation is calculated using the power
supply wattage rating.
Physical — Blades
PowerEdge M915
Height
Width
Depth
Weight (maximum)
PowerEdge M910
Height
Width
Depth
Weight (maximum)
PowerEdge M820
Height
Width
10
1200 BTU/hr (maximum)
Under typical input voltage conditions and over the
entire system ambient operating range, the inrush
current may reach 55 A per power supply for 10 ms or
less.
16 A, 200 V AC to 240 V AC, 50 Hz/60 Hz (3000 W power
supply)
16 A, 100 V AC to 240 V AC, 50 Hz/60 Hz (2700 W power
supply)
2700 W
Molex # 394260002 at PSU end,
mating connector Molex # 39422-0012
1205 BTU/hr (maximum)
Under typical input voltage conditions and over the
entire system ambient operating range, the inrush
current may reach 120 A per power supply for 10 ms or
less.
75 A, 48 V DC to 60 V DC
38.5 cm (15.2 inch)
5 cm (2 inch)
48.6 cm (19.2 inch)
12.7 kg (28 lb)
38.5 cm (15.2 inch)
5 cm (2 inch)
48.6 cm (19.2 inch)
13.1 kg (29 lb)
38.5 cm (15.2 inch)
5 cm (2 inch)